Amarok 2011 ➤ , Beetle 2012 ➤ , Bora 1999 ➤ , CC 2010 ➤ , CC 2012 ➤ , ...
Air conditioning system with refrigerant R134a - Edition 10.2014
Possible deviation Possible cause of fault Rectifying fault
from specification
•
Expansion valve de‐ – Renew ex‐
fective
pansion
valve.
– Recharge re‐
frigerant cir‐
cuit.
– Repeat
check.
Note
♦ If no fault can be found for this complaint, purge (clean) re‐
frigerant circuit with refrigerant R134a ⇒ page 67 . If this is not
possible in your workshop, blow through refrigerant circuit with
compressed air and dry with nitrogen ⇒ page 65 .
♦ Check the measured values of the evaporator output temper‐
ature sender - G263- or evaporator temperature sensor -
G308- and actuation of the air conditioner compressor
regulating valve - N280- . If the measured value of the evap‐
orator output temperature sender - G263- or the evaporator
temperature sender - G308- is faulty, the evaporator may ice
up or the cooling output will not be achieved.
♦ If a repeat test after the expansion valve has been renewed
indicates that the air conditioning system is still not operating
correctly, refit the expansion valve and purge the refrigerant
circuit with compressed air and nitrogen. Then renew the air lk
conditioner compressor and receiver.
♦ In this case, the evaporator may ice up although the correct
quantity of refrigerant is present in the refrigerant circuit.
♦ If the expansion valve is defective (always closed or not open‐
ing wide enough) the air conditioner compressor regulating
valve - N280- will be set to maximum power and the low-pres‐
sure value will fall to the diagram value or less (the air condi‐
tioner compressor is drawing the refrigerant out of the low-
pressure side). However, since no refrigerant can flow through
the expansion valve, the required cooling power is not deliv‐
ered, and it can be that the high-pressure value does not rise
at all or not enough, since no energy exchange is occurring.
Possible deviation from specifica‐
tion
Possible cause of fault
Rectifying fault
•
High pressure increases only
slightly above the pressure
measured when the engine is
stopped.
♦ Actuation of air conditioner compressor reg‐ – Check actuation of
ulating valve - N280- is defective.
air conditioner com‐
pressor regulating
valve - N280- .
•
•
Low pressure falls only slightly.
The required cooling output is
not delivered.
10. Checking pressures on vehicles
151