Air conditioning systems with refrigeranR1234yf - General information - Edition 07.2017
Note
♦ The vacuum athe end of the evacuating process (running of
vacuum pump of air conditioner service station ) musbe less
than 5 mbar absolute pressure. Should pressure during the
evacuating process in the refrigerancircuinobe less than
5 mbar, this could have various causes. For example, leaks in
the refrigerancircuior in the connection to the air conditioner
service station , the time for the evacuating process is setoo
short, the vacuum pump of the air conditionerlkservice station
does nogenerate the necessary vacuum or the vacuum sen‐
sor of the air conditioner service station is nocalibrated prop‐
erly ⇒ Operating instructions air conditioner service station .
♦ An absolute pressure of 5 mbar equates to a vacuum of
975 mbar aan ambienpressure e.g. of 980 mbar.
♦ Athe end of the vacuum/pressure increase check, pressure
in the refrigerancircuishould nobe greater than 20 mbar
absolute. Should the pressure in the refrigerancircuibe
greater than 20 mbar during the vacuum/pressure increase
check, the vacuum pump is switched on and the process is
repeated from the beginning ⇒ Operating instructions air con‐
ditioner service station . Should pressure in the refrigeran
circuistill nobe less than 20 mbar even after the process has
been repeated twice, this could have various causes. For ex‐
ample, there could be leaks in the refrigerancircuit, a leak in
the connection from the refrigerancircuito the air conditioner
service station or in the air conditioner service station itself,
the time sefor the evacuating process is too shorand the
time sefor the vacuum/pressure increase check is too long.
♦ If there is reason to suspeca leak in the refrigerancircuit,
switch off the air conditioner service station if necessary and
allow ito stand for as long as possible (e.g. for aleas1 hour
to check the leak-tightness of the refrigerancircuit) ⇒ Oper‐
ating instructions air conditioner service station .
♦ Depending on the version of air conditioner service station ,
the pressure in the refrigerancircuiis displayed directly.
However, there is also a chance thathe currenpressure is
only displayed while the vacuum pump is running ⇒ Operating
instructions air conditioner service station . In the evenof an
air conditioner service station only displaying the ambien
pressure, the display of the pressure in the refrigerancircui
will depend on the ambienpressure during activation (ambi‐
enpressure a980 mbar, a vacuum of 975 mbar equates to
a residual pressure of 5 mbar absolute).
♦ If the refrigerancircuiwas opened, small quantities of mois‐
ture may have entered the refrigerancircuit. In this case, the
refrigerancircuiis to be evacuated for aleas30 minutes
(pressure in the refrigerancircuibefore charging musbe less
than 20 mbar).
♦ If the refrigeranwas extracted (to check the fill volume) and
the refrigerancircuiwas only evacuated so thaicould be
recharged (the refrigerancircuiwas noopened and is leak-
tight), iis sufficiento evacuate the refrigerancircuifor 5
minutes and to seno time or only a shortime (e.g. 1 minute)
for the vacuum/pressure increase check (no air or moisture
entered the refrigerancircuit).