Advertisement

Advertisement

Air conditioning system -> 2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air conditioning compressor for Your Volkswagen Touran 4 Door Second Generation (2015-2022)

Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
In the event of the following fault “High pressure normal, low  
pressure too low”, please note the following: With this fault,  
there is a chance that the evaporator could ice up even though  
the refrigerant volume in the circuit is OK.  
If the fault exists in a shut-off valve that may be installed in the  
system (shut-off valve does not open), the refrigerant circuit  
needs to be cleaned (flushed with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ). With this fault,  
it is sufficient to check actuation of the shut-off valve. If this is  
OK, renew the shut-off valve.  
If the fault is in the air conditioner compressor regulating valve  
- N280- (the regulating valve is not activated, but the air con‐  
ditioner compressor still runs), it is not necessary to clean the  
refrigerant circuit (flush with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ). In this case it is  
sufficient to renew the air conditioner compressor (observe  
quantity of refrigerant oil in compressor).  
If the expansion valve is defective (always closed or not open‐  
ing wide enough) the air conditioner compressor regulating  
valve - N280- will be set to maximum power and the low pres‐  
sure value will fall to the diagram value or less (the air condi‐  
tioner compressor extracts refrigerant from the low pressure  
side). However, since no refrigerant can flow through the ex‐  
pansion valve, the required cooling output is not reached, the  
high pressure may also not rise or only marginally since no  
energy exchange is taking place. With this fault, it is not nec‐  
essary to clean the refrigerant circuit (flush with R1234yf re‐  
frigerant ⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
Renewing the expansion valve is sufficient.  
Check the measured values of the evaporator output temper‐  
ature sender - G263- and actuation of the air conditioner  
compressor regulating valve - N280- . If the measured value  
lk  
of -G263- is faulty, the evaporator could ice up or the cooling  
output may not be reached ⇒ Vehicle diagnostic tester in “Gui‐  
ded Fault Finding” mode - air conditioning system.  
Possible deviation from specification during pressure test  
♦ The air conditioner compressor is noisy (especially immediately after being switched on),  
♦ The requisite cooling output is reached.  
♦ High pressure normal or too high  
♦ The low pressure is normal or too high (the specification is not always reached)  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
201  
lk  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ Actuation of the air conditioner compressor regulating valve - N280- is defective.  
– Check actuation of the air conditioner compressor regulating valve - N280- and repair if necessary ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode - air conditioning system.  
♦ Check function of -N280- ; if necessary remove -N280- and check for dirt ⇒ Vehicle diagnostic tester in  
“Guided Fault Finding” mode - air conditioning system, ⇒ “1.5 Renewing components”, page 79 and ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (workshop manual for specific vehicle).  
♦ Renew -N280- or air conditioner compressor ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Air conditioner compressor (vehicle-specific workshop manual).  
♦ If dirt is found in the refrigerant circuit, clean the refrigerant circuit (flush with R1234yf refrigerant) and renew  
the expansion valve and desiccant bag/desiccant cartridge (or renew the receiver/reservoir)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 , ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Too much refrigerant or refrigerant oil in the refrigerant circuit  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably greater (more than 100 g) than the prescribed fill volume  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), there was  
too much refrigerant in the refrigerant circuit Recharge refrigerant circuit and repeat test.  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally higher than the  
prescribed fill volume (less than 100 g) ⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-  
specific workshop manual), there is too much refrigerant oil in the refrigerant circuit Clean the refrigerant  
circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 , recharge with the correct  
volume of refrigerant and refrigerant oil and repeat the test.  
♦ Expansion valve defective  
♦ If a shut-off valve is installed in the refrigerant circuit and it does not open correctly or at all ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve and desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
♦ The air conditioner compressor is defective.  
– If it is not possible to find a fault on any of the components and the extracted refrigerant volume equates  
to the specifications, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . If when cleaning the refrigerant circuit no overly high volume  
of refrigerant is found, renew the air conditioner compressor ⇒ “1.5 Renewing components”, page 79 , ⇒  
Heating, air conditioning; Rep. gr. 00 ; Repair instructions; Checking cooling output (vehicle-specific work‐  
shop manual) and ⇒ Heating, air conditioning; Rep. gr. 87 ; Air conditioner compressor (vehicle-specific  
workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat the test  
⇒ “2.14.4 Checking pressures with air conditioning system switched on - vehicles with mechanical air  
conditioning compressor”, page 183  
202  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
The cause for this fault could also be too much refrigerant oil  
in the refrigerant circuit. Overfilling with refrigerant oil can oc‐  
cur if the refrigerant oil level was not checked after the air  
conditioner compressor was renewed. If there is too much re‐  
frigerant oil in the refrigerant circuit, clean the refrigerant circuit  
(flush with R1234yf refrigerant).  
⇒ “1.6 Cleaning refrigerant circuit”, page 92  
If the expansion valve (or a shut-off valve that may be installed  
lk  
in the system) is defective (always closed or not opening wide  
enough) the air conditioner compressor regulating valve -  
N280- will be set to maximum power and the low pressure  
value will fall to the diagram value or less (the air conditioner  
compressor extracts refrigerant from the low pressure side).  
Since no refrigerant can flow through the expansion valve,  
however, the cooling output is not reached and the high pres‐  
sure may also not increase or only increase slightly owing to  
there being no energy exchange ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Possible deviation from specification during pressure test  
♦ The required cooling output is not reached.  
♦ The high pressure and low pressure equate to the specification  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
203  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume roughly equates to the prescribed fill volume, measured value of evapo‐  
rator output temperature sender - G263- , actuation of air conditioner compressor regulating valve - N280- ,  
function of expansion valve faulty or fault in a different component (see below).  
♦ Measured value of evaporator output temperature sender - G263- faulty.  
– Check measured value and installation of -G263- ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
function - air conditioning system and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of fitting locations  
- air conditioning system ⇒ Heating, air conditioning; Rep. gr. 87 ; Air conditioner compressor (vehicle-  
specific workshop manual).  
♦ Actuation of the air conditioner compressor regulating valve - N280- is defective.  
– Check the actuation of -N280- and, if necessary, repair ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode - air conditioning system.  
♦ Expansion valve defective  
lk  
♦ If a shut-off valve is installed in the refrigerant circuit and it does not open correctly or at all ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Touch the refrigerant circuit by hand to feel for a drop in temperature ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual). If a drop in temperature is felt on a component,  
if there is a kink or bottle-neck in the hose or pipeline, renew this component. In the event of a blockage or  
if no fault can be found, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve and desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
♦ Too much refrigerant oil in the refrigerant circuit  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally higher than the  
prescribed fill volume (less than 100 g) ⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-  
specific workshop manual), there is too much refrigerant oil in the refrigerant circuit Clean the refrigerant  
circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 , recharge with the correct  
volume of refrigerant and refrigerant oil and repeat the test.  
♦ Expansion valve defective  
♦ If a shut-off valve is installed in the refrigerant circuit and it does not open correctly or at all ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve and desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat the test  
⇒ “2.14.4 Checking pressures with air conditioning system switched on - vehicles with mechanical air  
conditioning compressor”, page 183  
204  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
Check the measured values of the evaporator output temper‐  
lk  
ature sender - G263- and actuation of -N280- . If the measured  
value of -G263- is faulty, the evaporator could ice up or the  
cooling output will not be reached ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of fitting  
locations - air conditioning system (vehicle-specific workshop  
manual).  
Overfilling with refrigerant oil can occur if the refrigerant oil  
level was not checked after the air conditioner compressor  
was renewed.  
If the expansion valve is defective (always open) the evapo‐  
rator temperature will no longer be controlled so that only  
gaseous refrigerant exits the evaporator. It is then possible  
that under certain operating conditions, drops of liquid will be  
drawn into the air conditioner compressor, which will hen  
cause noise (because liquid is incompressible).  
If there is too much refrigerant oil in the circuit, empty the air  
conditioner compressor and, if fitted, renew the reservoir/re‐  
ceiver (or desiccant cartridge) ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop  
manual). After cleaning the refrigerant circuit (flushing with  
R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 , pour the correct  
amount of refrigerant oil in the circuit ⇒ Heating, air condi‐  
tioning; Rep. gr. 00 ; Technical data (vehicle-specific work‐  
shop manual).  
2.14.5  
Checking pressures with air condition‐  
ing system switched on - vehicles with  
electrical air conditioning compressor  
Checking pressures ⇒ page 205  
Specifications for pressures in refrigerant circuit on vehicles with‐  
out heat pump ⇒ page 210  
Specifications for pressures in refrigerant circuit on vehicles with  
heat pump ⇒ page 234  
Checking pressures  
Note  
Work on the refrigerant circuit that involves the air conditioner  
service station (checking the pressures in this case) can usually  
be carried out without the need to de-energise the high-voltage  
system.  
– To minimise the number of automatic engine starts during  
testing and measuring while operational readiness is active,  
charge the vehicle batteries e.g. with battery charger 60A -  
VAS 5904- in battery back-up mode ⇒ Electrical system; Rep.  
gr. 27 ; Battery; Charging battery and ⇒ Electrical system;  
Rep. gr. 93 ; General warnings for work on the high-voltage  
system .  
– For test and measurement work that requires the vehicle's  
drive system to be active (READY) or the ignition to be switch‐  
ed on, move the selector lever to position “P”, activate the  
2. Working with air conditioner service station  
GETth  
205  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
parking brake and arrange the tools needed so that they can‐  
not come into contact with moving components of the engine  
and so that they cannot even come near to components that  
turn when the engine is running.  
Note  
Also move the selector lever to position “P”, and activate the  
parking brake before performing test and measurement work  
for which the ignition must be switched on but where the ve‐  
hicle's drive system does not need to be active (READY).  
lk  
Operational readiness (vehicle’s drive system) is displayed in  
the control unit in dash panel insert - J285- via the “Powerme‐  
ter” ⇒ owner's manual .  
Activating and deactivating vehicle drive system ⇒ Owner's  
manual (observe display in control unit in dash panel insert -  
J285- while doing so).  
– On vehicles with high-voltage system, switch off “stationary air  
conditioning” function (deactivate)⇒ Owner's Manual and ⇒  
Operating instructions of infotainment / MMI .  
– Switch off ignition.  
– Connect the air conditioner service station  
⇒ “2.2 Connecting air conditioner service station to refrigerant  
circuit”, page 131 .  
Note  
If a problem is encountered in just one evaporator on vehicles with  
two evaporators (one evaporator in the heater and air conditioning  
unit and one evaporator on the heat exchanger for high-voltage  
battery), check the pressures in the refrigerant circuit Check the  
line connection between the evaporator that is causing the prob‐  
lem and the end of the line at the distribution point for the refrig‐  
erant lines (for a bottle-neck or blockage). If no fault can be found,  
empty the refrigerant circuit and recharge it with the prescribed  
amount of refrigerant. Then check the pressures and the cooling  
output of the air conditioning system again. If the problem per‐  
sists, check / renew the following components: If the problem is  
only encountered at the evaporator in the heating and air condi‐  
tioning unit, check the evaporator in the heating and air condi‐  
tioning unit (it is open in unactuated state and allows refrigerant  
to flow through). Renew the expansion valve on the evaporator in  
the heater and air conditioning unit if no fault can be found in the  
shut-off valve. If the problem is only encountered on the evapo‐  
rator in the heat exchanger for high-voltage battery, check actua‐  
tion of the shut-off valve on the expansion valve on the evaporator  
in the heat exchanger for high-voltage battery (it is closed in un‐  
actuated state and does not allow refrigerant to flow through) ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
Conditions for testing  
The air conditioner service station is connected to the refrig‐  
erant circuit  
⇒ “2.2 Connecting air conditioner service station to refrigerant  
circuit”, page 131 .  
Observe the conditions for testing pressures in the refrigerant  
circuit with the ignition switched off ⇒ page 176 .  
The pressures in the refrigerant circuit comply with the speci‐  
fications with the ignition switched off  
206  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
⇒ “2.14.3 Checking pressures in the refrigerant circuit with the  
ignition switched off”, page 176 .  
Observe the conditions for testing thelckooling output ⇒ Heat‐  
ing, air conditioning; Rep. gr. 00 ; Repair instructions; Check‐  
ing cooling output (vehicle-specific workshop manual).  
Note  
The switching pressures for actuation of the electrical air con‐  
ditioner compressor - V470- and the radiator fan - V7- are  
vehicle-specific ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode - air conditioning system and battery regulation.  
The pressures must be measured at the service connections;  
the fitting locations of these connections are vehicle-specific  
⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
The engine is at operating temperature (at an ambient tem‐  
perature less than 25°C).  
Note  
Should the engine not be at operating temperature, take the  
vehicle for a short drive.  
To test the cooling output, the engine does not have to be at  
operating temperature. However, to demand a certain cooling  
output from the air conditioning system at an ambient temper‐  
ature of less than 25°C, the engine is required to be warm if  
ambient temperatures are low.  
To minimise the number of automatic engine starts during  
testing and measuring while operational readiness is active,  
charge the vehicle batteries e.g. with battery charger 60A -  
VAS 5904- in battery back-up mode ⇒ Electrical system; Rep.  
gr. 27 ; Battery; Charging battery and ⇒ Electrical system;  
Rep. gr. 93 ; General warnings for work on the high-voltage  
system .  
– Activate operational readiness (engine must not run) ⇒ own‐  
er's manual .  
– Set the air conditioning system to maximum cooling output ⇒  
Heating, air conditioning; Rep. gr. 00 ; Repair instructions;  
Checking cooling output (vehicle-specific workshop manual).  
The electrical air conditioner compressor - V470- is actuated  
and runs ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode - air conditioning system and battery regulation as well  
as ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
2. Working with air conditioner service station  
GETth  
207  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
Note  
Actuation of the electrical air conditioning compressor is initi‐  
ated by the vehicle electronics. The engine speed has no  
influence on the cooling output of the air conditioning system.  
The air conditioner compressor is currently not activated at the  
maximum specified speed (of approx. 8500 rpm) when the  
vehicle is stationary or driving slowly (up to a vehicle speed of  
45 km/h). The air conditioner compressor speed is restricted  
to approx. 5000 rpm.  
Actuation of the electrical air conditioning compressor can be  
monitored by guided fault finding ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
battery regulation.  
All of the conditions for testing marked with * are pertinent to  
a certain vehicle and are described in the vehicle-specific  
workshop manual ⇒ Heating, air conditioning; Rep. gr. 00 ;  
Repair instructions; Checking cooling output (vehicle-specific  
workshop manual).  
If the air conditioner compressor is not actuated with operational  
readiness active:  
– Determine the cause, e.g. by interrogating the event memory  
of the air conditioning system, and rectify it ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode - air conditioning  
system and battery regulation.  
The radiator and condenser are clean (clean if necessary) * ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual) and ⇒ Engine, mechanicals;  
Rep. gr. 19 ; Radiator/radiator fan .  
The heat insulation on the expansion valve is OK and mounted  
correctly * ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
The air ducts, covers and seals are OK and mounted correctly  
* ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of fitting  
locations - air conditioning system (vehicle-specific workshop  
manual).  
No faults are found during diagnosis of the air conditioning  
system (with operational readiness (vehicle’s drive system)  
active and the air conditioning system switched on). No com‐  
pressor deactivation condition is shown in the measured valve  
block ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode - air conditioning system and battery regulation.  
The various pressure/temperature senders and temperature  
sensors on or in the refrigerant circuit supply plausible values  
during operation of the air conditioning system, check ⇒ Ve‐  
hicle diagnostic tester in “Guided Fault Finding” mode and ⇒  
Heating, air conditioning; Rep. gr. 87 ; Overview of fitting lo‐  
cations - air conditioning system . If no fault can be found,  
extract the refrigerant.  
The rate of air flow through the dust and pollen filter is not  
impaired by dirt * ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Overview of fitting locations - air conditioning system (vehicle-  
specific workshop manual).  
The heater and air conditioner does not draw any secondary  
air at highest fresh air blower speed. evaporator and heater  
not drawing in secondary air at maximum fresh-air blower  
speed * ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair in‐  
structions; Checking cooling output (vehicle-specific work‐  
shop manual).  
208  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
The air duct flaps in the heater and air conditioner unit, heater  
and evaporator reach their end position * ⇒ Heating, air con‐  
ditioning; Rep. gr. 00 ; Repair instructions; Checking cooling  
output (vehicle-specific workshop manual).  
Fresh-air intake ducts beneath bonnet and in passenger com‐  
partment as well as corresponding water drain valves OK* ⇒  
Heating, air conditioning; Rep. gr. 87 ; Overview of fitting lo‐  
cations - air conditioning system (vehicle-specific workshop  
manual).  
The vehicle is not exposed to the sun's rays ⇒ Heating, air  
conditioning; Rep. gr. 00 ; Repair instructions; Checking cool‐  
ing output (vehicle-specific workshop manual).  
Ambient temperature is above 15°C.  
All dash panel air vents are open.*  
Setting e.g. on operating and display unit for front air conditioning  
system - E87- (and operating and display unit for rear air condi‐  
tioning system - E265- on vehicles with two heater and air con‐  
ditioning units) * ⇒ Heating, air conditioning system; Rep. gr. 00 ;  
Repair instructions; Checking cooling output (vehicle-specific  
workshop manual) and ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Overview of fitting locations - air conditioning system .  
Setting e.g. on -E87- *:  
– Select “Auto” mode (air conditioner compressor switched on).  
– Set temperature to “cold” or “LO” for the driver and front pas‐  
senger side (and the rear on the left and right in vehicles with  
two heating and air conditioning units).*  
Setting on -J301- *:  
– Press A/C button and Rec or recirculate buttons.*  
lk  
– Turn rotary temperature knob in direction of “cold” stop.*  
– Set rotary fresh air blower switch to “4” (maximum fresh air  
blower speed).*  
The following conditions for testing should then be met in the sys‐  
tem:  
The radiator fan - V7- is running or the radiator fan - V7- and  
radiator fan 2 - V177- are running (at least stage 1) * ⇒ Heat‐  
ing, air conditioning; Rep. gr. 00 ; Repair instructions; Check‐  
ing cooling output (vehicle-specific workshop manual) and ⇒  
Engine, mechanicals; Rep. gr. 19 ; Radiator/radiator fan .  
Note  
On certain versions, the radiator fan cuts in only after the pressure  
in the refrigerant circuit has exceeded a pre-set value ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode - air conditioning  
system and battery regulation.  
The fresh air blower - V2- (and the rear fresh air blower - V80-  
on vehicles with two heating and air conditioning units) is  
running at maximum speed.*  
The air recirculation flap/fresh air flap is in “recirculation  
mode” (within 1 minute after starting the vehicle, the air flow  
flap closes and the air recirculation flap opens).*  
The coolant shut-off valve is closed * ⇒ Heating, air condi‐  
tioning; Rep. gr. 00 ; Repair instructions; Checking cooling  
output (vehicle-specific workshop manual) and ⇒ Heating, air  
2. Working with air conditioner service station  
GETth  
209  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
conditioning; Rep. gr. 87 ; Overview of fitting locations - air  
conditioning system (vehicle-specific workshop manual).  
The valves of the pump-valve unit are closed and the coolant  
circulation pump is not delivering * ⇒ Heating, air conditioning;  
Rep. gr. 00 ; Repair instructions; Checking cooling output  
(vehicle-specific workshop manual) and ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Overview of fitting locations - air  
conditioning system (vehicle-specific workshop manual).  
Note  
Actuation of the electrical air conditioning compressor is initi‐  
ated by the vehicle electronics. The engine speed has no  
influence on the cooling output of the air conditioning system  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode -  
air conditioning system and battery regulation.  
The air conditioner compressor is currently not activated at the  
maximum specified speed (of approx. 8500 rpm) when the  
vehicle is stationary or driving slowly (up to a vehicle speed of  
45 km/h). The air conditioner compressor speed is restricted  
to approx. 5000 rpm.  
Actuation of the electrical air conditioning compressor can be  
monitored by guided fault finding ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
battery regulation.  
The pressures must be measured at the service connections;  
the fitting locations of these connections are vehicle-specific  
⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Specifications for pressures in the refrigerant circuit  
♦ Specifications for pressures in refrigerant circuit on vehicles  
without heat pump ⇒ page 210  
lk  
♦ Specifications for pressures in refrigerant circuit on vehicles  
with heat pump ⇒ page 234  
Note  
The specified and actual speeds for actuation of the electrical  
air conditioner compressor - V470- and the radiator fan - V7-  
are vehicle-specific ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode - air conditioning system and battery reg‐  
ulation.  
The pressures must be measured at the service connections;  
the fitting locations of these connections are vehicle-specific  
⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Specifications for pressures in refrigerant circuit on vehicles with‐  
out heat pump  
♦ Observe the test prerequisites ⇒ page 205 .  
– Watch the pressure display (e.g. pressure gauge) of the air  
conditioner service station .  
210  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
The switching pressures for actuation of the electrical air con‐  
ditioner compressor - V470- and the radiator fan -V7- / -V177-  
are vehicle-specific ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode - air conditioning system and battery reg‐  
ulation.  
The pressures must be measured at the service connections;  
the fitting locations of these connections are vehicle-specific  
⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
High-pressure side:  
From the output pressure (when the pressure gauge is connec‐  
ted) rising up to a maximum overpressure of 20 bar (depending  
on the ambient temperature and operating conditions of the air  
conditioning system).  
Low-pressure side:  
From the output pressure (when connecting the pressure gauge)  
dropping to a value of between 1.5 and 2.3 bar absolute pressure  
(depending on required cooling output).  
Speed of air conditioner compressor:  
lk  
Between 800 and 8500 rpm depending on the required cooling  
output (currently maximum 5000 rpm with vehicle stationary).  
2. Working with air conditioner service station  
GETth  
211  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
The temperature of the air after the evaporator, the current air  
conditioner compressor speed and the pressure of the refrig‐  
erant on the high-pressure side are displayed as a measured  
value from various control units depending on the vehicle (e.g.  
operating and display unit, -E87- , -J255- , thermal manage‐  
ment control unit - J1024- and air conditioning system control  
unit - J301- ) ⇒ Vehicle diagnostic tester in “Guided Fault Find‐  
ing” mode - air conditioner compressor and battery regulation.  
In the event of a very high cooling output (e.g. at high outside  
temperatures and high fresh air blower speed), the air condi‐  
tioner compressor is initially incapable of changing the pres‐  
sure on the low pressure side to the required level (e.g. for a  
certain period after switching on the air conditioning system).  
The air conditioner compressor is not activated with the max.  
specified (of approx. 8500 rpm), if the vehicle stands still or  
drives slowly (up to a vehicle speed of 45 km/h). The air con‐  
ditioner compressor speed is then limited to 5000 rpm. The  
maximum permissible air conditioner compressor speed limit  
is not lifted until a vehicle speed greater than approx. 45 km/  
h is reached. The output (delivery rate) of the air conditioner  
compressor at an air conditioner compressor speed of  
5000 rpm, a high ambient temperature and high fresh air blow‐  
er speed (unfavourable ambient conditions) is initially no lon‐  
ger sufficient to bring the pressure on the low pressure side  
down to the specified value. To check the regulating behaviour  
of the air conditioner compressor under these conditions, e.g.  
only actuate the fresh air blower with approx. 40% of the max‐  
imum voltage and check the pressures at reduced fresh air  
blower speed ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode - air conditioning system and battery regulation  
and ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair instruc‐  
lk  
tions; Checking cooling output (vehicle-specific workshop  
manual).  
If the demand on the cooling output is low (e.g. at an ambient  
temperature of 20°C and a low fresh air blower speed), pres‐  
sure on the high pressure side may only increase up to a value  
of 6 to 7 bar (the energy exchange is low, the refrigerant is  
cooled down quickly in the condenser). To check the regulat‐  
ing behaviour and the pressures in the refrigerant circuit under  
these conditions, e.g. actuate the fresh air blower with maxi‐  
mum voltage, set the air conditioning system to maximum  
heating output and activate air recirculation ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode - air conditioning  
system and ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair  
instructions; Checking cooling output (vehicle-specific work‐  
shop manual).  
Under unfavourable conditions (very high ambient tempera‐  
tures, high atmospheric humidity), the pressure on the high  
pressure side can increase to a maximum of 29 bar.  
The specified speed of the air conditioner compressor is dis‐  
played by various control units depending on the vehicle (e.g.  
operating and display unit, -E87- , -J255- and air conditioning  
system control unit - J301- ⇒ Vehicle diagnostic tester) in  
“Guided Fault Finding” mode - air conditioning system.  
The high-pressure measured by various senders (e.g. high-  
pressure sender - G65- , pressure sender for refrigerant circuit  
- G805- or refrigerant pressure and temperature sender -  
G395- ) is displayed as a measured value depending on the  
vehicle (e.g. by -E87- , -J301- , thermal management control  
unit - J1024- or -J255- ) ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode - air conditioner compressor.  
212  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
The low pressure adjusts itself depending on the speed of the  
air conditioner compressor and the regulating characteristic of  
the expansion valve within the performance band of the air  
conditioner compressor in the tolerance range (1.5 to 2.3 over‐  
pressure).  
For this test, the specified speed of the air conditioner com‐  
pressor must be greater than 1500 rpm ⇒ Vehicle diagnostic  
tester in “Guided Fault Finding” mode - air conditioning sys‐  
tem.  
For the “maximum cooling output” setting, the specified speed  
of the air conditioner compressor is regulated at approx. 4000  
to 5000 rpm. This value is vehicle-specific and is displayed as  
a measured value by the respective control unit (e.g. operating  
and display unit, -E87- , -J255- or thermal management control  
unit - J1024- ⇒ Vehicle diagnostic tester) in “Guided Fault  
Finding” mode - air conditioning system and battery regulation.  
Absolute pressure means that 0 bar corresponds to an abso‐  
lute vacuum. The normal ambient pressure corresponds to 1  
bar absolute. On the scales of most pressure gauges, 0 bar  
corresponds to an absolute pressure of 1 bar (can be seen  
from -1 bar mark below 0) ⇒ Vehicle diagnostic tester in “Gui‐  
ded Fault Finding” mode - air conditioning system.  
If, on a vehicle with 2 evaporators (one in the heater and air  
conditioner unit and one for battery cooling), the temperature  
lk  
measured at one evaporator meets the specification or falls  
below the specification, while on the other evaporator, how‐  
ever, the requisite specification is not reached, regulation  
works as follows: the respective control unit (e.g. battery reg‐  
ulation control unit or thermal management control unit )  
makes the electrical air conditioner compressor run at a higher  
speed via additional controls units (e.g. power and control  
electronics for electric drive and control unit for air conditioning  
compressor ) (which results in the cooling output of the air  
conditioning system rising and pressure on the low pressure  
side falling along with the evaporator temperature). If the spec‐  
ification then falls below the minimum level at one evaporator,  
the respective control unit (e.g. battery regulation control unit )  
actuates the shut-off valves (e.g. refrigerant shut-off valve 1  
or refrigerant shut-off valve 2 ) in such a way that the evapo‐  
rator that is too cold no longer has refrigerant flowing through  
it ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
- air conditioning system and battery regulation as well as ⇒  
Heating, air conditioning; Rep. gr. 00 ; Repair instructions;  
Checking cooling output (vehicle-specific workshop manual)  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system (vehicle-specific  
workshop manual).  
Since the output of the evaporator in the battery cooling mod‐  
ule is considerably lower than the output of the evaporator in  
the heating and air conditioning unit, the requisite specified  
temperature in the battery cooling module may still be reached  
if there is insufficient refrigerant in the circuit but the specified  
temperature in the evaporator of the heating and air condi‐  
tioning unit will no longer be reached (even though the air  
conditioner compressor is actuated at a higher speed) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Repair instructions;  
Checking cooling output (vehicle-specific workshop manual)  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant cir‐  
cuit (vehicle-specific workshop manual).  
2. Working with air conditioner service station  
GETth  
213  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviations from specification,  
cause and rectification  
♦ The requisite cooling output in the evap‐ ⇒ page 216  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ High pressure remains constant or in‐  
creases only slightly (above the pressure  
measured when the engine is stopped).  
♦ High pressure drops quickly to the spec‐  
ification or lower.  
♦ The requisite cooling output in the evap‐ ⇒ page 218  
orator in the heating and air conditioning  
unit (and in the evaporator for battery  
cooling) is reached initially. However, af‐  
ter a while or after an extended period of  
lk  
operation, the cooling output is no longer  
adequate.  
♦ The high pressure and the low pressure  
are normal to start with  
♦ After some time, the high pressure rises  
above the specification, the low pressure  
still equates to the specification or it  
drops below the specification.  
♦ The requisite cooling output in the evap‐ ⇒ page 220  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ The high pressure equates to the speci‐  
fication  
♦ The low pressure is too low (lower than  
the specification)  
♦ The air conditioner compressor is noisy ⇒ page 222  
(especially immediately after being  
switched on),  
♦ The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit and / or in the evaporator for battery  
cooling is not reached.  
♦ High pressure normal or too high  
♦ Low pressure too high (specification is  
not reached)  
♦ The requisite cooling output in the evap‐ ⇒ page 224  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ High pressure and low pressure normal  
(equate to specification)  
214  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviations from specification,  
cause and rectification  
♦ The requisite cooling output in the evap‐ ⇒ page 226  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ The high pressure equates to the speci‐  
fication  
♦ The low pressure equates to the specifi‐  
cation or is too low  
♦ The requisite cooling output in the evap‐ ⇒ page 227  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
lk  
cooling module) is not reached.  
♦ The high pressure equates to the speci‐  
fication  
♦ Low pressure drops quickly to the spec‐  
ification or lower.  
♦ The requisite cooling output in the evap‐ ⇒ page 228  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ The requisite cooling output is then not  
reached at the evaporator in the heater  
and air conditioning unit (the cooling out‐  
put at the evaporator in the battery cool‐  
ing module is OK).  
♦ High pressure increases only slightly  
(above the pressure measured when the  
engine is stationary) or equates to the  
specification.  
♦ Low pressure drops (possibly quickly) to  
the specification or lower.  
♦ The requisite cooling output in the evap‐ ⇒ page 229  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ The high pressure increases beyond the  
specified value  
♦ Low pressure drops quickly to the spec‐  
ification or lower.  
♦ The requisite cooling output is then not ⇒ page 232  
reached at the evaporator for battery  
cooling (the cooling output at the evapo‐  
rator in the heater and air conditioning  
unit is OK).  
♦ High pressure equates to the specifica‐  
tion or increases only slightly (above the  
pressure measured when the engine is  
stationary).  
♦ Low pressure drops to the specification  
or lower.  
2. Working with air conditioner service station  
GETth  
215  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviations from specification,  
cause and rectification  
♦ The requisite cooling output in the evap‐ ⇒ page 233  
lk  
orator of the heating and air conditioning  
unit (and in the evaporator for the battery  
cooling module) is not reached.  
♦ High pressure does not increase or only  
marginally above the pressure with the  
engine stationary  
♦ The low pressure does not drop or only  
marginally  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ High pressure remains constant or increases only slightly (above the pressure measured when the air  
conditioner compressor is stationary).  
♦ High pressure drops quickly to the specification or lower.  
Possible causes for deviation from specification and rectification  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves. If no fault is found, renew the expansion  
valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual)  
♦ Actuation of air conditioner compressor (and if fitted refrigerant shut-off valve 1 and refrigerant shut-off  
valve 2 ) faulty ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning system and  
battery regulation, ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair instructions; Checking cooling output  
(vehicle-specific workshop manual), ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of fitting locations  
- air conditioning system (vehicle-specific workshop manual) and ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Air conditioner compressor (vehicle-specific workshop manual).  
– Check actuation and the function of the air conditioner compressor (and if fitted the shut-off valves, e.g.  
refrigerant shut-off valve 1 , refrigerant shut-off valve 2 ) and repair if necessary ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation. If this is OK, extract the  
refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective and must be  
renewed ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the refrigerant shut-off valves (if fitted) is defective (closed). Check the function and renew if nec‐  
essary ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning system and battery  
regulation and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit; System overview - refrigerant  
circuit  
♦ Bottle-neck or blockage in refrigerant circuit (e.g. in refrigerant line between service connection on “low  
pressure side” and air conditioner compressor) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
– If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
– If a hose or pipe is kinked or crushed, renew this component ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective and must be  
renewed ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ A refrigerant shut-off valve is defective (closed). Check the function and renew ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation and ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
216  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
lk  
2. Working with air conditioner service station  
GETth  
217  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
lk  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
If, with this problem, no fault is found during diagnosis, check  
the refrigerant circuit for a bottle-neck or blockage (a bottle-  
neck or blockage in the refrigerant circuit can also lead to one  
of these complaints). If nothing is found here either, clean the  
refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
Check the measured values of the evaporator output temper‐  
ature sender - G263- and, if fitted, temperature sensor before  
evaporator for hybrid battery and temperature sensor after  
evaporator for hybrid battery as well as actuation of air condi‐  
tioner compressor via the respective control unit ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode - air condi‐  
tioning system and battery regulation.  
If there is a fault in the measured value of -G263- , temperature  
sensor before evaporator for hybrid battery or temperature  
sensor after evaporator for hybrid battery (depending on the  
vehicle ⇒ Vehicle diagnostic tester in “Guided Fault Finding” -  
air conditioning system and battery regulation), problems may  
also be encountered in the cooling output or the evaporator  
could ice up.  
In the event of a fault in a temperature sensor, the evaporator  
may ice up even though the correct quantity of refrigerant is  
present in the refrigerant circuit.  
If, after repeating the test when the expansion valve has been  
renewed, the air conditioning system is not operating correctly,  
clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Then renew the  
air conditioner compressor and desiccant cartridge (or reser‐  
voir/receiver) ⇒ Heating, air conditioning; Rep. gr. 87 ; Re‐  
frigerant circuit (vehicle-specific workshop manual).  
If the expansion valve on the evaporator in the heater and air  
conditioning unit or the shut-off valve is defective (always  
closed or does not open sufficiently), the air conditioner com‐  
pressor is actuated at the maximum output and low pressure  
drops to the specification or lower (the air conditioner com‐  
pressor draws in refrigerant from the low pressure side). Since  
no refrigerant can flow through the expansion valve, however,  
the cooling output is not reached and the high pressure may  
also not increase or only increase slightly owing to there being  
no energy exchange ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode - air conditioning system and battery reg‐  
ulation and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
The evaporator in the heater and air conditioning unit has a  
considerably higher output than the evaporator for battery  
cooling. Depending on the way the drive battery - A2- is cooled  
(depending on the vehicle ⇒ Vehicle diagnostic tester in “Gui‐  
ded Fault Finding” - air conditioning system and battery regu‐  
lation), the refrigerant shut-off valve 2 on the expansion valve  
in the battery cooling module is currently only actuated from a  
certain battery temperature by the respective control unit (e.g.  
by battery regulation control unit ) so that the power consumed  
by the evaporator for battery cooling is not or barely increased  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode -  
air conditioning system and battery regulation as well as ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual).  
218  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator in the heating and air conditioning unit (and in the evaporator  
for battery cooling) is reached initially. However, after a while or after an extended period of operation, the  
cooling output is no longer adequate.  
♦ The high pressure and the low pressure are normal to start with  
♦ After some time, the high pressure rises above the specification, the low pressure still equates to the  
specification or it drops below the specification.  
Possible causes for deviation from specification and rectification  
♦ Radiator, condenser contaminated or actuation of the radiator is not OK  
– Check actuation of the radiator fan and repair if necessary ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode - air conditioning system.  
– Check condenser for contamination and clean if necessary ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual) and ⇒ Engine, mechanicals; Rep. gr. 19 ; Radiator/  
radiator fan .  
♦ Actuation or the function of the air conditioner compressor (or, if fitted, the refrigerant shut-off valve 1 or  
refrigerant shut-off valve 2 ) is faulty.  
♦ Moisture in refrigerant circuit  
– Check the actuation of the air conditioner compressor (and if fitted the refrigerant shut-off valve 1 and  
refrigerant shut-off valve 2 ) and check the measured value of the evaporator output temperature sender  
- G263- ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode.  
– If actuation of the air conditioner compressor (and, if fitted, the refrigerant shut-off valve 1 and refrigerant  
shut-off valve 2 ) as well as the measured value of -G263- are OK, extract the refrigerant from the refrigerant  
circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
♦ Too much refrigerant in the refrigerant circuit  
lk  
♦ Expansion valve defective  
♦ If a shut-off valve is installed in the refrigerant circuit and it does not open correctly or at all ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Moisture in refrigerant circuit  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably greater (more than 100 g) than the prescribed fill volume  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), there was  
too much refrigerant in the refrigerant circuit Recharge refrigerant circuit and repeat test.  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally higher than the  
prescribed fill volume (less than 100 g) ⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-  
specific workshop manual), there is too much refrigerant oil in the refrigerant circuit Clean the refrigerant  
circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 , recharge with the correct  
volume of refrigerant and refrigerant oil and repeat the test.  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve and desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
219  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
If there is too much refrigerant oil in the circuit, empty the air  
conditioner compressor and renew the reservoir/receiver (or  
desiccant cartridge) ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual). After  
cleaning the refrigerant circuit (flushing with R1234yf refriger‐  
ant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 , pour in the  
correct amount of refrigerant oil in the refrigerant circuit ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-  
lk  
specific workshop manual).  
Check the measured values of the evaporator output temper‐  
ature sender - G263- and actuation of the air conditioner  
compressor. If the measured value of -G263- or actuation of  
the air conditioner compressor is faulty, the evaporator could  
ice up or the cooling output will not be reached ⇒ Vehicle di‐  
agnostic tester in “Guided Fault Finding” mode - air condition‐  
ing system and battery regulation as well as ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Overview of fitting locations - air  
conditioning system ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Air conditioner compressor (vehicle-specific workshop man‐  
ual).  
In this case, the evaporator may ice up even though the correct  
volume of refrigerant is present in the refrigerant circuit.  
A fault in -G263- or / and, if fitted, in the refrigerant shut-off  
valve for hybrid battery can also cause the refrigerant circuit  
to ice up. With this complaint, also take note of the measured  
value of -G263- and the temperature sensor after evaporator  
for hybrid battery (on vehicles with a battery cooling module)  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode -  
air conditioning system and battery regulation and ⇒ Heating,  
air conditioning; Rep. gr. 87 ; Overview of fitting locations - air  
conditioning system (vehicle-specific workshop manual).  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ The high pressure equates to the specification  
♦ The low pressure is too low (lower than the specification)  
Possible causes for deviation from specification and rectification  
220  
Rep. gr.87 - Air conditioning system  
GETth  
lk  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves. If no fault is found, renew the expansion  
valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual)  
♦ Actuation or the function of the air conditioner compressor or, if fitted, the refrigerant shut-off valve 1 /  
refrigerant shut-off valve 2 is faulty.  
– Check actuation and the function of the air conditioner compressor and, if fitted, the refrigerant shut-off  
valve 1 / refrigerant shut-off valve 2 ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air con‐  
ditioning system and battery regulation.  
– Clean refrigerant circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
♦ The expansion valve in the heater and air conditioning unit or, if fitted, in the evaporator for battery cooling  
is defective.  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit (and for the evaporator  
for battery cooling) as well as the desiccant bag/desiccant cartridge (or reservoir/receiver).  
♦ Air conditioner compressor is defective  
– Renew air conditioner compressor ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Air conditioner compressor (vehicle-specific workshop manual).  
– If dirt is found in the refrigerant circuit, clean the refrigerant circuit (flush with R1234yf refrigerant) and renew  
the expansion valve and desiccant bag/desiccant cartridge (or receiver/reservoir)  
⇒ “1.5 Renewing components”, page 79 and ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
221  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
In the event of the following fault “High pressure normal, low  
pressure too low”, please note the following: With this fault,  
there is a chance that the evaporator could ice up even though  
the refrigerant volume in the circuit is OK.  
If the fault exists in the air conditioner compressor (it is not  
actuated but still works), it is not necessary to clean (flush with  
R1234yf refrigerant) the refrigerant circuit  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . With this fault, it  
is sufficient to renew the air conditioner compressor (take note  
of refrigerant oil in air conditioner compressor)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Technical data (vehicle-specific  
workshop manual).  
If the problem is with the air conditioner compressor (the air  
conditioner compressor is actuated at excessively high speed  
by the control unit for air conditioning compressor ), the refrig‐  
erant circuit does not have to be cleaned (by flushing with  
R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ). With this fault,  
it is sufficient to renew the air conditioner compressor (take  
note of refrigerant oil in air conditioner compressor) ⇒ Heating,  
air conditioning; Rep. gr. 00 ; Technical data (vehicllke-specific  
workshop manual) and ⇒ Heating, air conditioning; Rep. gr.  
87 ; Air conditioner compressor (vehicle-specific workshop  
manual).  
If the expansion valve (or one of the two expansion valves) is  
defective (always closed or does not open sufficiently), the air  
conditioner compressor is also actuated at the maximum out‐  
put and pressure drops on the low pressure side to the spec‐  
ification or lower (the air conditioner compressor draws in  
refrigerant from the low pressure side). However, since no re‐  
frigerant can flow through the defective expansion valve, the  
required cooling output in the downstream evaporator is not  
reached, the high pressure may also not rise or only marginally  
since no energy exchange is taking place. The air conditioner  
compressor can be actuated at a higher speed, however,  
since the requisite cooling output in one evaporator is not  
reached. The same also applies if operation or actuation of the  
refrigerant shut-off valve 1 or refrigerant shut-off valve 2 is  
faulty ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode - air conditioning system and battery regulation and ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual).  
Check the measured values of the evaporator output temper‐  
ature sender - G263- (and, if fitted, the measured values of the  
temperature sensor before evaporator for hybrid battery and  
temperature sensor after evaporator for hybrid battery ) as well  
as actuation of the air conditioner compressor by the control  
unit for air conditioning compressor . If the measured value of  
-G263- (of the temperature sensor before evaporator for hy‐  
brid battery , the temperature sensor after evaporator for  
hybrid battery - G757- ) or actuation of the air conditioner com‐  
pressor are faulty, the evaporator can ice up or the requisite  
cooling output will not be reached ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioner compressor  
and battery regulation and ⇒ Heating, air conditioning; Rep.  
gr. 87 ; Overview of fitting locations - air conditioning system  
(vehicle-specific workshop manual).  
222  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ The air conditioner compressor is noisy (especially immediately after being switched on),  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit and / or in the evap‐  
orator for battery cooling is not reached.  
♦ High pressure normal or too high  
♦ Low pressure too high (specification is not reached)  
Possible causes for deviation from specification and rectification  
♦ Actuation or the function of the air conditioner compressor or, if fitted, the refrigerant shut-off valve 1 /  
refrigerant shut-off valve 2 is faulty.  
♦ Too much refrigerant or refrigerant oil in the refrigerant circuit.  
– Check the actuation and function of the air conditioner compressor and, if fitted, the refrigerant shut-off  
valve 1 / refrigerant shut-off valve 2 ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air con‐  
ditioning system and battery regulation. Repair if necessary. If no fault can be found, extract the refrigerant  
from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably greater (more than 100 g) than the prescribed fill volume  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), there was  
too much refrigerant in the refrigerant circuit Recharge refrigerant circuit and repeat test.  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally higher than the  
prescribed fill volume (less than 100 g) ⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-  
specific workshop manual), there is too much refrigerant oil in the refrigerant circuit Clean the refrigerant  
circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 , recharge with the correct  
volume of refrigerant and refrigerant oil and repeat the test.  
♦ Expansion valve defective  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit (and for the evaporator  
lk  
for battery cooling) as well as the desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
♦ Air conditioner compressor is defective  
– Renew air conditioner compressor ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Air conditioner compressor (vehicle-specific workshop manual).  
– If dirt is found in the refrigerant circuit, clean the refrigerant circuit (flush with R1234yf refrigerant) and renew  
the expansion valve and desiccant bag/desiccant cartridge (or receiver/reservoir)  
⇒ “1.5 Renewing components”, page 79 and ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
223  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
Note  
The cause for this fault could also be too much refrigerant oil  
in the refrigerant circuit. Overfilling with refrigerant oil can oc‐  
cur if e.g. the refrigerant oil level was not checked after the air  
conditioner compressor was renewed  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air  
conditioning; Rep. gr. 00 ; Technical data (vehicle-specific  
workshop manual). If there is too much refrigerant oil in the  
refrigerant circuit, clean the refrigerant circuit (flush with  
R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
If the expansion valve on the evaporator in the heater and air  
conditioning unit (or for the evaporator for battery cooling) is  
defective (always closed or does not open sufficiently), the air  
conditioner compressor is actuated at the maximum output  
and low pressure drops to the specification or lower (the air  
conditioner compressor draws in refrigerant from the low pres‐  
sure side). However, since no refrigerant can flow through the  
expansion valve, the required cooling output is not reached,  
the high pressure may also not rise or only marginally since  
no energy exchange is taking place. The same also applies if  
operation or actuation of the refrigerant shut-off valve 1 or re‐  
frigerant shut-off valve 2 is faulty ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
battery regulation and ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ High pressure and low pressure normal (equate to specification)  
Possible causes for deviation from specification and rectification  
224  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ Actuation or the function of the air conditioner compressor and, if fitted, the refrigerant shut-off valve 1 or  
refrigerant shut-off valve 2 is faulty.  
♦ Insufficient refrigerant in refrigerant circuit.  
– Check the actuation and function of the air conditioner compressor and/or, if fitted, the refrigerant shut-off  
valve 1 / refrigerant shut-off valve 2 ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air con‐  
ditioning system and battery regulation. Repair if necessary ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual). If no fault can be found, extract the refrigerant from  
the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), the expansion  
valve for the evaporator or an installed shut-off valve in the heater and air conditioning unit is defective.  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the refrigerant shut-off valves (if fitted) is defective (closed). Check the function and renew if nec‐  
essary ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning system and battery  
regulation and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop  
manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Too much refrigerant oil in the refrigerant circuit.  
lk  
– Clean refrigerant circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit (and for the evaporator  
for battery cooling) as well as the desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
225  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
The cause for this fault could also be too much refrigerant oil  
in the refrigerant circuit. Overfilling with refrigerant oil can oc‐  
cur if e.g. the refrigerant oil level was not checked after the air  
conditioner compressor was renewed  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air  
conditioning; Rep. gr. 00 ; Technical data (vehicle-specific  
workshop manual). If there is too much refrigerant oil in the  
refrigerant circuit, clean the refrigerant circuit (flush with  
R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
If the expansion valve on the evaporator in the heater and air  
conditioning unit (or for the evaporator for battery cooling) is  
defective (always closed or does not open sufficiently), the air  
conditioner compressor is actuated at the maximum output  
and low pressure drops to the specification or lower (the air  
conditioner compressor draws in refrigerant from the low pres‐  
sure side). However, since no refrigerant can flow through the  
expansion valve, the required cooling output is not reached,  
the high pressure may also not rise or only marginally since  
no energy exchange is taking place. The same also applies if  
operation or actuation of the refrigerant shut-off valve 1 or re‐  
frigerant shut-off valve 2 is faulty ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and  
battery regulation and ⇒ Heating, air conditioning; Rep. gr.  
lk  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ The high pressure equates to the specification  
♦ The low pressure equates to the specification or is too low  
Possible causes for deviation from specification and rectification  
226  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ Actuation of the air conditioner compressor (and/or if fitted the refrigerant shut-off valve 1 , refrigerant shut-  
off valve 2 ) is faulty ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning system  
and battery regulation.  
– Check the actuation and function of the air conditioner compressor (and if fitted the refrigerant shut-off  
valve 1 , refrigerant shut-off valve 2 ) and repair if necessary ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode - air conditioning system and battery regulation. If this is OK, extract the refrigerant from the  
refrigerant circuit.  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for the  
leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual) ⇒ Heating,  
air conditioning; Rep. gr. 00 ; Technical data . Check the function of the refrigerant shut-off valves ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ A refrigerant shut-off valve is defective (closed). Check the function and renew ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation and ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Too much refrigerant oil in the refrigerant circuit.  
– Clean refrigerant circuit (flush with R1234yf refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
lk  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit (and for the evaporator  
for battery cooling) as well as the desiccant bag/desiccant cartridge (or reservoir/receiver)  
⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 218 and  
⇒ page 226 .  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ The high pressure equates to the specification  
♦ Low pressure drops quickly to the specification or lower.  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
227  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ Actuation or function of air conditioner compressor defective.  
♦ Constriction or obstruction in refrigerant circuit  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation. If no fault can be found,  
touch the refrigerant circuit by hand to feel for a temperature drop ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If a temperature drop is determined in a component. If a hose or pipe is kinked or crushed, renew this  
component ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for the  
lk  
leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), check the  
function of the expansion valve and shut-off valves ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant  
circuit (vehicle-specific workshop manual).  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ A refrigerant shut-off valve is defective (closed). Check the function and renew ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation and ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 218 and  
⇒ page 226 .  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ The requisite cooling output is then not reached at the evaporator in the heater and air conditioning unit  
(the cooling output at the evaporator in the battery cooling module is OK).  
♦ High pressure increases only slightly (above the pressure measured when the air conditioner compressor  
is stationary) or equates to the specification.  
♦ Low pressure drops (possibly quickly) to the specification or lower.  
Possible causes for deviation from specification and rectification  
228  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for the  
leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), check the  
function of the expansion valve and shut-off valves ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant  
circuit (vehicle-specific workshop manual).  
♦ The expansion valve for the evaporator in the heater and air conditioning unit is defective ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the refrigerant shut-off valves is defective (closed). Check the function and renew if necessary  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning system and battery regulation  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If fitted, check the function of the installed shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
– Renew the expansion valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Bottle-neck or blockage in refrigerant circuit (e.g. in refrigerant line between service connection on “low  
pressure side” and air conditioner compressor) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
lk  
(vehicle-specific workshop manual).  
♦ Actuation of the air conditioner compressor is faulty ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode - air conditioning system and battery regulation.  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode - air conditioning system and battery regulation. If no fault can be found,  
touch the refrigerant circuit by hand to feel for a temperature drop ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If a temperature drop is determined in a component. If a hose or pipe is kinked or crushed, renew this  
component (the defective expansion valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual). If there is a blockage, clean the refrigerant circuit (flush with R1234yf  
refrigerant) ⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
– If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Renew the expansion valve for the evaporator in the heater  
and air conditioning unit (and for the evaporator for battery cooling) as well as the desiccant bag/desiccant  
cartridge (or reservoir/receiver) ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 218 .  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ The high pressure increases beyond the specified value  
♦ Low pressure drops quickly to the specification or lower.  
2. Working with air conditioner service station  
GETth  
229  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
Possible causes for deviation from specification and rectification  
♦ Actuation or function of air conditioner compressor defective.  
♦ Constriction or obstruction in refrigerant circuit  
♦ Expansion valve defective  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
lk  
in “Guided Fault Finding” mode - air conditioning system and battery regulation. If no fault can be found,  
touch the refrigerant circuit by hand to feel for a temperature drop ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If a temperature drop is determined in a component. If a hose or pipe is kinked or crushed, renew this  
component (the defective expansion valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual).  
– If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Renew the expansion valve for the evaporator in the heater  
and air conditioning unit (and for the evaporator for battery cooling) as well as the desiccant bag/desiccant  
cartridge (or reservoir/receiver) ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ There is too little refrigerant in the refrigerant circuit.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for the  
leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), check the  
function of the refrigerant shut-off valve ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
230  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
If the function of the air conditioning system is not OK when  
the test is repeated, renew the expansion valve and desiccant  
bag/desiccant cartridge (or reservoir/receiver) and, if fitted, the  
refrigerant shut-off valve ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
In this case, the evaporator may ice up even though the correct  
volume of refrigerant is present in the refrigerant circuit.  
If the expansion valve on the evaporator in the heater and air  
conditioning unit or the refrigerant shut-off valve 1 is defective  
(always closed or does not open sufficiently), the air condi‐  
tioner compressor is actuated at the maximum output and low  
pressure drops to the specification or lower (the air conditioner  
compressor draws in refrigerant from the low pressure side).  
Since no refrigerant can flow through the expansion valve (the  
refrigerant shut-off valve ), however, the cooling output is not  
reached and the high pressure may also not increase or only  
increase slightly owing to there being no energy exchange  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode -  
air conditioning system and battery regulation and ⇒ Heating,  
lk  
air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-spe‐  
cific workshop manual).  
If the expansion valve on the evaporator for battery cooling is  
defective (or the function or actuation of the refrigerant shut-  
off valve 2 is faulty), completely closed or does not open  
sufficiently, the air conditioner compressor is likewise actuated  
with the maximum output (the requisite temperatures in the  
battery cooling module are not reached). The pressure on the  
low pressure side only drops to the specification or lower if, at  
the same time, no cooling output is required in the heater and  
air conditioning unit (the refrigerant shut-off valve 1 is actuated  
and is closed). The air conditioner compressor extracts refrig‐  
erant on the low pressure from both evaporators. Since no  
refrigerant can flow through the expansion valve in the heater  
and air conditioning unit (the refrigerant shut-off valve 1 ),  
however, and the cooling output for battery cooling is not  
reached (there is a fault in the area of battery cooling), the  
electric air conditioning compressor is actuated at a higher  
speed. However, since no more refrigerant can flow, the pres‐  
sure on the low pressure side drops below the specified value  
and the high pressure may also not increase or only increase  
slightly due to the absence of an energy exchange ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode - air condi‐  
tioning and battery control ⇒ Heating, air conditioning; Rep.  
gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Since the output of the evaporator for battery cooling is con‐  
siderably lower than the output of the evaporator in the heating  
and air conditioning unit, the requisite specified temperature  
for battery cooling may still be reached if there is insufficient  
refrigerant in the circuit but the specified temperature in the  
evaporator of the heating and air conditioning unit will not be  
reached (even though the air conditioner compressor is actu‐  
ated at a higher speed).  
2. Working with air conditioner service station  
GETth  
231  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
If there is too much refrigerant in the refrigerant circuit, the air  
conditioner compressor must be emptied and the desiccant  
bag (desiccant cartridge) or reservoir/receiver renewed. After  
cleaning (flushing with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 the refrigerant cir‐  
cuit, pour the correct volume of refrigerant oil in the refrigerant  
circuit ⇒ Heating, air conditioning; Rep. gr. 00 ; Technical  
data; Approved refrigerant oils and refrigerant oil fill volumes  
(vehicle-specific workshop manual) and ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific  
workshop manual).  
Observe the additional information relating to this  
⇒ page 218 .  
Possible deviation from specification during pressure test  
♦ The requisite cooling output is then not reached at the evaporator for battery cooling (the cooling output at  
the evaporator in the heater and air conditioning unit is OK).  
♦ High pressure equates to the specificatlkion or increases only slightly (above the pressure measured when  
the engine is stationary).  
♦ Low pressure drops to the specification or lower.  
Possible causes for deviation from specification and rectification  
♦ Actuation or the function of the refrigerant shut-off valve 2 , a control motor, the blower or a temperature  
sensor in or on the battery cooling module is defective. Check and repair if necessary ⇒ Vehicle diagnostic  
tester in “Guided Fault Finding” mode - air conditioning system and battery regulation and ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ The expansion valve for the evaporator in the battery cooling module is defective.  
– Renew the expansion valve for the evaporator for battery cooling ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
– Check the function and actuation of the components for battery cooling ⇒ Vehicle diagnostic tester in  
“Guided Fault Finding” mode - air conditioning system and battery regulation. Check the refrigerant lines  
if no fault can be found.  
♦ Bottle-neck or blockage in refrigerant line to or from expansion valve on evaporator for battery cooling.  
– If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Renew the expansion valve for the evaporator in the heater  
and air conditioning unit (and for the evaporator for battery cooling) as well as the desiccant bag/desiccant  
cartridge (or reservoir/receiver) ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If a hose or pipe is kinked or crushed, renew this component ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
♦ Too little refrigerant in circuit.  
♦ Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
♦ If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g) ⇒  
Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for the  
leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
♦ If the extracted refrigerant volume equates to the prescribed fill volume or is marginally lower (max. 100 g)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), check the  
refrigerant shut-off valve 1 ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning  
system and battery regulation and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
232  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
To cool the drive battery - A2- (hybrid battery), the refrigerant  
shut-off valve 1 is only actuated by e.g. the battery regulation  
control unit from a certainlbkattery temperature. If, at this point,  
air conditioning operation has not already been activated, the  
electrical air conditioner compressor - V470- is actuated via  
the control unit for air conditioning compressor - J842- e.g. by  
the battery regulation control unit . The temperature of the air  
(or refrigerant) before and after the evaporator for battery cool‐  
ing is calculated by the respective control unit (e.g. battery  
regulation control unit ). If it is found that cooling down is in‐  
sufficient, this is stored in e.g. the battery regulation control  
unit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
- air conditioning system and battery regulation.  
The temperature of the air (or the coolant) and thereby the  
cooling output of the evaporator for battery cooling is deter‐  
mined by the integrated temperature sensor (it cannot cur‐  
rently be measured during operation with a thermometer) and  
can therefore only be checked by means of guided fault finding  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode -  
air conditioning system and battery regulation.  
Observe the additional information relating to this  
⇒ page 218 .  
Possible deviation from specification during pressure test  
♦ The requisite cooling output in the evaporator of the heating and air conditioning unit (and in the evaporator  
for the battery cooling module) is not reached.  
♦ High pressure does not increase or only marginally above the pressure with the engine stationary  
♦ The low pressure does not drop or only marginally  
Possible causes for deviation from specification and rectification  
♦ No actuation of air conditioner compressor ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode.  
♦ If fitted, refrigerant shut-off valve 1 defective (closed)  
– Check the actuation and function of the air conditioner compressor (and the refrigerant shut-off valve 1 ,  
refrigerant shut-off valve 2 ) ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode - air conditioning  
system and battery regulation. If no fault can be found, renew the expansion valve on the evaporator in the  
heating and air conditioning unit ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
♦ Bottle-neck or blockage in refrigerant circuit (e.g. in refrigerant line between service connection on “low  
pressure side” and air conditioner compressor).  
– If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Renew the expansion valve for the evaporator in the heater  
and air conditioning unit (and for the evaporator for battery cooling) as well as the desiccant bag/desiccant  
cartridge (or reservoir/receiver) ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If a hose or pipe is kinked or crushed, renew this component ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
♦ The air conditioner compressor is defective.  
– Renew air conditioner compressor ⇒ “1.5 Renewing components”, page 79 and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Air conditioner compressor (vehicle-specific workshop manual).  
Final measures  
2. Working with air conditioner service station  
GETth  
233  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Specifications for pressures in refrigerant circuit on vehicles with  
heat pump  
Note  
On vehicles with high-voltage system and heat pump, the re‐  
frigerant circuit is fitted with non-return valves and electrically  
actuated valves that regulate the flow of refrigerant in the re‐  
frigerant circuit depending on the prevailing operating status.  
These valves come in different versions ⇒ Heating, air con‐  
ditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific  
workshop manual) and ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode.  
On vehicles with “heat pump” function and/or “high-voltage  
lk  
battery cooling” function, high pressure is not always at the  
service connection on the high pressure side in all operating  
conditions of the air conditioning system. On these vehicles,  
depending on the operating status of the air conditioning sys‐  
tem, pressure in the refrigerant circuit on the high pressure  
side can only be measured via the pressure/temperature  
sender installed in the refrigerant circuit ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific work‐  
shop manual) and ⇒ Vehicle diagnostic tester “Guided Fault  
Finding” mode.  
The refrigerant circuit of the air conditioning system on these  
vehicles is used not only to cool the passenger compartment  
but also to cool the hybrid battery unit (via the coolant circuit  
for the high-voltage system) and to heat the passenger com‐  
partment (at low ambient temperatures) via the heat pump  
function. To ensure that these functions are effective, various  
valves, pressure and temperature senders as well as pumps  
in the refrigerant circuit and in the coolant circuit of the high-  
voltage system must be installed correctly and be in good  
working order ⇒ Heating, air conditioning; Rep. gr. 87 ; Re‐  
frigerant circuit (vehicle-specific workshop manual), ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode and ⇒ En‐  
gine, mechanicals; Rep. gr. 19 ; Cooling system/coolant  
To localise the potential cause of the malfunction, various rou‐  
tines have been stored in the basic settings of the thermal  
management control unit with which the “air conditioning cool‐  
ing”, “heat pump” and “cooling components of the high-voltage  
system” functions can be actuated ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode.  
High-pressure side:  
Rising from starting pressure (when pressure gauge is connec‐  
ted) to maximum 20 bar.  
234  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
Note  
Depending on the location of the service connection on the high  
pressure side and on the operating status, the high pressure can  
only be measured using pressure/temperature sensors installed  
in the refrigerant circuit ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
Low-pressure side:  
From the output pressure (when connecting the pressure gauge)  
dropping to a value of between 1.5 and 2.3 bar absolute pressure  
(depending on required cooling output).  
Speed of air conditioner compressor:  
Between 800 and 8500 rpm depending on the required cooling  
output (currently maximum 5000 rpm with vehicle stationary).  
2. Working with air conditioner service station  
GETth  
235  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
The temperature of the air after the evaporator, the current air  
conditioner compressor speed and the pressure of the refrig‐  
erant on the high pressure side are displayed as a measured  
by different control units depending on the vehicle (e.g. by the  
thermal management control unit , the operating and display  
unit for front air conditioning system or the Climatronic control  
unit ) ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system (vehicle-specific  
workshop manual) and ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode.  
In the event of a very high cooling output (e.g. at high outside  
temperatures and high fresh air blower speed), the air condi‐  
tioner compressor is initially incapable of changing the pres‐  
sure on the low pressure side to the required level (e.g. for a  
certain period after switching on the air conditioning system).  
The air conditioner compressor is not activated with the max.  
specified (of approx. 8500 rpm), if the vehicle stands still or  
drives slowly (up to a vehicle speed of 45 km/h). The air con‐  
ditioner compressor speed is then limited to 5000 rpm. The  
maximum permissible air conditioner compressor speed limit  
is not lifted until a vehicle speed greater than approx. 45 km/  
h is reached. The output (delivery rate) of the air conditioner  
compressor at an air conditioner compressor speed of  
5000 rpm, a high ambient temperature and high fresh air blow‐  
er speed (unfavourable ambient conditions) is initially no lon‐  
ger sufficient to bring the pressure on the low pressure side  
down to the specified value. To check the regulating behaviour  
of the air conditioner compressor under these conditions, e.g.  
only actuate the fresh air blower with approx. 40% of the max‐  
imum voltage and check the pressures at reduced fresh air  
blower speed ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode - air conditioning system and battery regulation  
lk  
and ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair instruc‐  
tions; Checking cooling output (vehicle-specific workshop  
manual).  
Under unfavourable conditions (very high ambient tempera‐  
tures, high atmospheric humidity), the pressure on the high  
pressure side can increase to a maximum of 29 bar.  
The specified speed of the air conditioner compressor is dis‐  
played as a measured value e.g. by the thermal management  
control unit ⇒ Vehicle diagnostic tester in “Guided Fault Find‐  
ing” mode.  
The pressure measured by various pressure/temperature  
senders in the refrigerant circuit (low or high pressure) de‐  
pending on the respective operating status is displayed as a  
measured value by the respective control unit ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating,  
air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-spe‐  
cific workshop manual).  
The low pressure adjusts itself depending on the speed of the  
air conditioner compressor and the regulating characteristic of  
the expansion valve (on the evaporator of the front heating and  
air conditioning unit) within the performance band of the air  
conditioner compressor in the tolerance range (1.5 to 2.3 over‐  
pressure).  
The specified speed of the air conditioner compressor must  
be greater than 1500 rpm for this test.  
236  
Rep. gr.87 - Air conditioning system  
GETth  
lk  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
For the “maximum cooling output” setting, the specified speed  
is regulated at approx. 4000 to 5000 rpm. This value is vehicle-  
specific and is displayed as a measured value by the respec‐  
tive control unit ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode.  
Absolute pressure means that 0 bar corresponds to an abso‐  
lute vacuum. The normal ambient pressure corresponds to 1  
bar absolute. On most pressure gauges, a reading of 0 bar  
corresponds to an absolute pressure of 1 bar (which can be  
identified by -1 bar under the 0 scale marking).  
If on a vehicle with 2 evaporators (one in the heating and air  
conditioning unit and one for cooling the high-voltage compo‐  
nents, e.g. the heat exchanger for the high-voltage battery)  
and 2 condensers (one on the front end for the air conditioning  
system and one as a heat exchanger for the heat pump func‐  
tion), the specifications for the measured temperatures or  
pressures are met on one component but not on another (de‐  
pending on the selected function), check actuation of the  
electrically actuated valves installed in the refrigerant circuit.  
When doing this, observe the pressure distribution in the re‐  
frigerant circuit depending on the installed non-return valves  
⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant cir‐  
cuit (vehicle-specific workshop manual).  
For the air conditioning system to function correctly, it is also  
important - depending on the selected function - for sufficient  
heat to be supplied to the respective heat exchangers and  
subsequently dissipated. Also note, therefore, the inclusion of  
the heat exchangers in the respective coolant circuit of the  
engine and the high-voltage system and the function of the  
pumps and valves installed therein ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode and ⇒ Heating, air condition‐  
ing; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop  
manual).  
Since the output of the evaporator for cooling on the high-volt‐  
age components (in the battery cooling module and in the heat  
exchanger for high-voltage battery) is lower than the output of  
the evaporator in the heating and air conditioning unit, the  
requisite specified temperature in the evaporator for cooling of  
the high-voltage components may still be reached if there is  
insufficient refrigerant in the circuit but the specified tempera‐  
ture in the evaporator of the heating and air conditioning unit  
is no longer reached (even though the air conditioner com‐  
pressor is actuated at a higher speed).  
Possible deviations from specification,  
cause and rectification  
High pressure remains constant or in‐ ⇒ page 239  
creases only slightly (above the pressure  
measured when the engine is stopped).  
High pressure drops quickly to the spec‐  
ification or lower.  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit and in the evaporator for cooling the  
high-voltage components is not reached.  
High pressure normal  
⇒ page 242  
Low pressure equates to specification  
The required cooling output is not  
reached.  
2. Working with air conditioner service station  
GETth  
237  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviations from specification,  
cause and rectification  
High pressure normal  
⇒ page 243  
Low pressure normal or too low (lower  
than specification)  
The requisite cooling output is then not  
reached at the evaporator in the heater  
and air conditioning unit (the cooling out‐  
put at the evaporator to cool the high-  
voltage components is OK).  
High pressure normal  
⇒ page 244  
Low pressure normal or too low (lower  
than specification)  
The requisite cooling output is then not  
reached at the evaporator to cool the  
high-voltage components (the cooling  
output at the evaporator in the heating  
lk  
and air conditioning unit is OK).  
High pressure does not increase or only ⇒ page 245  
marginally above the pressure with the  
engine stationary.  
The low pressure does not drop or only  
marginally.  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit and in the evaporator for cooling the  
high-voltage components is not reached.  
High pressure increases above specifi‐ ⇒ page 246  
cation  
Low pressure drops quickly to the spec‐  
ification  
The requisite cooling output in the evap‐  
orator of the front heating and air condi‐  
tioning unit (and/or in the evaporator  
used to cool the high-voltage compo‐  
nents) is not reached.  
The high pressure and low pressure are ⇒ page 248  
normal to start with but after a while the  
high pressure rises above the specifica‐  
tion and the low pressure drops to the  
specification or lower.  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit (and/or in the evaporator used to  
cool the high-voltage components) is not  
reached or no longer reached.  
High pressure and low pressure are nor‐ ⇒ page 249  
mal at first but after a longer drive the low  
pressure falls to below the specification  
(evaporator in heater and air condition‐  
ing unit iced up).  
238  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviations from specification,  
cause and rectification  
High pressure normal  
Low pressure too low  
⇒ page 251  
⇒ page 252  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit (and/or in the evaporator used to  
cool the high-voltage components) is not  
reached.  
High pressure normal or too high  
Low pressure too high  
The air conditioner compressor is noisy  
(especially immediately after being  
switched on)  
The requisite cooling output in the evap‐  
orator of the front heating and air condi‐  
tioning unit (and/or in the evaporator  
used to cool the high-voltage compo‐  
nents) is not reached.  
High pressure and low pressure normal ⇒ page 254  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit and in the evaporator for cooling the  
high-voltage components is not reached.  
lk  
or  
High pressure and low pressure normal  
The air conditioner compressor is noisy  
(especially immediately after being  
switched on)  
The requisite cooling output in the evap‐  
orator of the heating and air conditioning  
unit (and/or in the evaporator used to  
cool the high-voltage components) is not  
reached.  
High pressure and low pressure normal ⇒ page 255  
The requisite cooling output in the evap‐  
orator of the front heating and air condi‐  
tioning unit (and in the evaporator for  
cooling the high-voltage components) is  
not reached.  
The requisite cooling output is not  
reached in the heat exchanger for heat  
pump operation.  
Possible deviation from specification during pressure test  
High pressure remains constant or increases only slightly (above the pressure measured when the engine  
is stopped).  
High pressure drops quickly to the specification or lower.  
The requisite cooling output in the evaporator of the heating and air conditioning unit and in the evaporator  
for cooling the high-voltage components is not reached.  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
239  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Too little refrigerant in circuit.  
♦ Actuation of the air conditioner compressor or one of the valves installed in the refrigerant circuit faulty.  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system . If no fault can be found, extract the refrigerant.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves. If no fault is found, renew the expansion  
valve for the evaporator in the heater and air conditioning unit ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual)  
lk  
– Depending on the result, repair the actuation or renew the defective component (air conditioner compres‐  
sor, shut-off valve, expansion valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
240  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
To localise the potential cause of the malfunction, various rou‐  
tines have been stored in the basic settings of the respective  
control unit (e.g. in the thermal management control unit ) with  
which the “air conditioning cooling”, “heat pump” and “cooling  
components of the high-voltage system” functions can be ac‐  
tuated ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrig‐  
erant circuit (vehicle-specific workshop manual).  
If no fault is found with this complaint, first check actuation of  
the electrically actuated valves installed in the refrigerant cir‐  
cuit. If no fault can be found here, remove and check the non-  
return valves installed in the refrigerant circuit. If no fault can  
be found here either, clean the refrigerant circuit (flush with  
R1234yf refrigerant). A bottle-neck or a blockage in the refrig‐  
erant circuit can also result in one of these complaints ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual) and  
⇒ “1.6 Cleaning refrigerant circuit”, page 92  
On vehicles with “heat pump” function and/or “high-voltage  
battery cooling” function, high pressure is not always at the  
lk  
service connection on the high pressure side in all operating  
conditions of the air conditioning system. On these vehicles,  
depending on the operating status of the air conditioning sys‐  
tem, pressure in the refrigerant circuit on the high pressure  
side can only be measured via the pressure/temperature  
sender installed in the refrigerant circuit ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific work‐  
shop manual) and ⇒ Vehicle diagnostic tester “Guided Fault  
Finding” mode.  
Before commencing the repair work, check the measured val‐  
ues of the various pressure/temperature senders installed in  
the refrigerant circuit. If there is a fault in the measured value  
of a pressure/temperature sender, problems in the cooling  
output may also be experienced or the evaporator in the front  
heating and air conditioning unit could ice up ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific  
workshop manual), ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode and ⇒ Current flow diagrams, Electrical  
fault finding and Fitting locations.  
When checking the various functions (heat pump or cooling of  
the high-voltage battery) take note also of the actuation and  
function of the components of the coolant circuit that are rela‐  
ted to these functions ⇒ Heating, air conditioning; Rep. gr.  
87 ; Coolant circuit (vehicle-specific workshop manual).  
If, after repeating the test when the expansion valve has been  
renewed, the air conditioning system is not operating correctly,  
clean the refrigerant circuit (flush with R134a refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 . Then renew air  
conditioner compressor and receiver/desiccant cartridge.  
In the event of a fault in a temperature sensor, the evaporator  
may ice up even though the correct quantity of refrigerant is  
present in the circuit.  
2. Working with air conditioner service station  
GETth  
241  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
If the expansion valve on the evaporator in the heater and air  
conditioning unit is defective (always closed or does not open  
sufficiently), the air conditioner compressor is actuated at the  
maximum output and low pressure drops to the diagram value  
or lower (the air conditioner compressor draws in refrigerant  
from the low pressure side). Since refrigerant cannot flow via  
the expansion valve, however, the cooling output is not  
reached and the high pressure may also not increase or only  
increase slightly due to the absence of energy exchange ⇒ Ve‐  
hicle diagnostic tester in “Guided Fault Finding” mode - air  
conditioning system and battery regulation ⇒ Heating, air con‐  
lk  
ditioning; Rep. gr. 00 ; Repair information; Checking cooling  
output (vehicle-specific workshop manual).  
The evaporator in the heater and air conditioning unit has a  
higher output than the evaporator in the battery cooling mod‐  
ule. The expansion valve in front of this evaporator (the heat  
exchanger for cooling the components of the high-voltage sys‐  
tem) is currently actuated, depending on the version, only from  
or up to a certain battery temperature to cool the drive battery /  
hybrid battery unit (hybrid battery) by the respective control  
unit so that the energy exchange through this evaporator is not  
increased or only marginally ⇒ Vehicle diagnostic tester in  
“Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 00 ; Repair instructions; Checking cooling output  
(vehicle-specific workshop manual).  
If there is too much refrigerant in the refrigerant circuit, the air  
conditioner compressor must also be emptied (flushed) and  
the receiver/desiccant cartridge renewed. After cleaning the  
refrigerant circuit (flushing with R134a refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 , pour in the cor‐  
rect amount of refrigerant oil in the circuit (in the air conditioner  
compressor) ⇒ Heating, air conditioning; Rep. gr. 00 ; Tech‐  
nical data (vehicle-specific workshop manual).  
Possible deviation from specification during pressure test  
High pressure normal  
Low pressure equates to specification  
The required cooling output is not reached.  
Possible causes for deviation from specification and rectification  
242  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Too little refrigerant in circuit.  
♦ Shut-off valve before the expansion valve for the evaporator in the front heating and air conditioning unit  
defective.  
♦ One of the other valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating,  
air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Expansion valve for the evaporator in the front heating and air conditioning unit defective.  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system . If no fault can be found, extract the refrigerant.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves if no fault is found ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual)  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
lk  
tioning compressor”, page 205  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Depending on the result, repair the actuation or renew the defective component (shut-off valve/expansion  
valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 241 .  
Possible deviation from specification during pressure test  
High pressure normal  
Low pressure normal or too low (lower than specification)  
The requisite cooling output is then not reached at the evaporator in the heater and air conditioning unit  
(the cooling output at the evaporator to cool the high-voltage components is OK).  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
243  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Too little refrigerant in circuit.  
♦ Actuation of air conditioner compressor is defective.  
♦ Expansion valve for the evaporator in the front heating and air conditioning unit defective.  
♦ Shut-off valve before the expansion valve for the evaporator in the front heating and air conditioning unit  
defective.  
♦ One of the other valves installed in the refrigerant circuit is defective or does not work properly.  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system . If no fault can be found, extract the refrigerant.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves if no fault is found ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual)  
lk  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Depending on the result, repair the actuation or renew the defective component (shut-off valve/expansion  
valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 241 .  
Possible deviation from specification during pressure test  
High pressure normal  
Low pressure normal or too low (lower than specification)  
The requisite cooling output is then not reached at the evaporator to cool the high-voltage components (the  
cooling output at the evaporator in the heating and air conditioning unit is OK).  
Possible causes for deviation from specification and rectification  
244  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the pumps or one of the valves in the coolant circuit of the high-voltage battery is defective or does  
not work properly ⇒ Heating, air conditioning; Rep. gr. 87 ; Coolant circuit (vehicle-specific workshop  
manual).  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
lk  
♦ Bottle-neck or blockage in the refrigerant line to or from the expansion valve on the evaporator used to cool  
the high-voltage components  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system .  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Check the function and actuation of the components used to cool the high-voltage components ⇒ Vehicle  
diagnostic tester in “Guided Fault Finding” mode - air conditioning system, air conditioner compressor and  
battery regulation  
– Depending on the result, repair the actuation or renew the defective component (shut-off valve, expansion  
valve, coolant pump, coolant shut-off valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit  
(vehicle-specific workshop manual) and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (ve‐  
hicle-specific workshop manual).  
– Check the lines of the refrigerant circuit. If a hose or pipe is kinked or crushed, renew this component.  
– If no fault can be found, clean the refrigerant circuit (flush with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 241 .  
Possible deviation from specification during pressure test  
High pressure does not increase or only marginally above the pressure with the engine stationary.  
The low pressure does not drop or only marginally.  
The requisite cooling output in the evaporator of the heating and air conditioning unit and in the evaporator  
for cooling the high-voltage components is not reached.  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
245  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
Possible deviation from specification during pressure test  
♦ No actuation of the air conditioner compressor. The air conditioner compressor is not driven.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Bottle-neck or blockage in refrigerant circuit (e.g. in refrigerant line between service connection on “low  
pressure side” and air conditioner compressor).  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Depending on the result, repair the actuation or renew the defective component (air conditioner compres‐  
sor, shut-off valve, expansion valve) ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
– Check the lines of the refrigerant circuit. If a hose or pipe is kinked or crushed, renew this component ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Touch the refrigerant circuit by hand during operation to feel for temperature drops (bottle-neck or block‐  
age). If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
– If no fault can be found in the air conditioner compressor, renew the air conditioner compressor  
⇒ “1.5 Renewing components”, page 79  
– If no fault can be found, clean the refrigerant circuit (flush with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 241 .  
Possible deviation from specification during pressure test  
High pressure increases above specification  
Low pressure drops quickly to the specification  
The requisite cooling output in the evaporator of the front heating and air conditioning unit (and/or in the  
evaporator used to cool the high-voltage components) is not reached.  
Possible causes for deviation from specification and rectification  
246  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
lk  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ Actuation or function of air conditioner compressor defective.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Constriction or obstruction in refrigerant circuit  
♦ Expansion valve defective  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Check the lines of the refrigerant circuit. If a hose or pipe is kinked or crushed, renew this component ⇒  
Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Touch the refrigerant circuit by hand during operation to feel for temperature drops (bottle-neck or block‐  
age). If there is a blockage, clean the refrigerant circuit (flush with R1234yf refrigerant)  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 .  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
247  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
In this case, the evaporator may ice up even though the correct  
volume of refrigerant is present in the refrigerant circuit.  
If the expansion valve on the evaporator in the heater and air  
conditioning unit or the previously installed shut-off valve is  
defective (always closed or does not open sufficiently), the air  
conditioner compressor is actuated at the maximum output  
and low pressure drops to the specification or lower (the air  
conditioner compressor draws in refrigerant from the low pres‐  
sure side). Since no (or too little) refrigerant can flow via the  
expansion valve, however, the cooling output is not reached  
and the high pressure may also not increase or only increase  
slightly due to the absence of energy exchange ⇒ Vehicle di‐  
agnostic tester in “Guided Fault Finding” mode - air condition‐  
ing system and battery regulation ⇒ Heating, air conditioning;  
Rep. gr. 00 ; Repair information; Checking cooling output (ve‐  
hicle-specific workshop manual).  
If the expansion valve in front of the evaporator used to cool  
the high-voltage components is defective (or function and ac‐  
tuation are faulty), permanently closed or does not open far  
enough, the air conditioner compressor is likewise actuated  
with maximum output (the requisite temperatures in the heat  
exchanger are not reached). The pressure on the low pressure  
side then only drops to the specification or lower if, at the same  
time, no cooling output is required in the heating and air con‐  
ditioning unit. The air conditioner compressor extracts refrig‐  
erant on the low pressure from both evaporators. Since no  
refrigerant can flow through the expansion valve in the front  
heating and air conditioning unit, however, and the cooling  
output in the evaporator used to cool the high-voltage compo‐  
nents is not reached (there is a fault in the area of the evapo‐  
rator used to cool the high-voltage components), the electrical  
air conditioning compressor is actuated with a higher speed.  
However, no refrigerant can flow, which causes pressure on  
the low pressure side to drop below the specification. High  
pressure may not rise or only marginally as no energy ex‐  
change takes place. The same applies if a valve in the refrig‐  
erant circuit is not OK, if there is a fault with integration of the  
evaporator for cooling of the high-voltage components in the  
refrigerant circuit of the high-voltage system or a pump or  
valve installed there is not OK. Here, the heat exchanger for  
high-voltage battery does actually cool down but the cooled  
coolant does not reach the high-voltage components that need  
to be cooled down ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode and ⇒ Heating, air conditioning system; Rep.  
gr. 87 ; Coolant circuit (vehicle-specific workshop manual).  
lk  
Further notes regarding this ⇒ page 241 .  
Possible deviation from specification during pressure test  
The high pressure and low pressure are normal to start with but after a while the high pressure rises above  
the specification and the low pressure drops to the specification or lower.  
The requisite cooling output in the evaporator of the heating and air conditioning unit (and/or in the evap‐  
orator used to cool the high-voltage components) is not reached or no longer reached.  
Possible causes for deviation from specification and rectification  
248  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Actuation and function of air conditioner compressor faulty ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ Moisture in refrigerant circuit  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system .  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If no fault can be found, clean the refrigerant circuit (flush with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
lk  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
Observe the information relating to this ⇒ page 241 .  
Possible deviation from specification during pressure test  
High pressure and low pressure are normal at first but after a longer drive the low pressure falls to below  
the specification (evaporator in heater and air conditioning unit iced up).  
Possible causes for deviation from specification and rectification  
2. Working with air conditioner service station  
GETth  
249  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Actuation and function of air conditioner compressor faulty ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Moisture in refrigerant circuit  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system .  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If no fault can be found, renew the desiccant bag/desiccant cartridge (or reservoir/receiver) and evacuate  
the refrigerant circuit for at least 3 hours.  
Final measures  
lk  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
Note  
With this complaint, there is no need to clean the refrigerant  
circuit (flush with R1334yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ) as there is usu‐  
ally only a small amount of moisture in the system, which can  
be removed by a longer evacuation period.  
If this complaint occurs after a longer period of operation or  
only occasionally due to moisture in the refrigerant circuit (low  
pressure falls below the specification and the evaporator ices  
up), renewing the dryer (fitted within the receiver) is sufficient.  
Refrigerant circuit is then to be evacuated for at least 3 hours.  
In this case, the evaporator may ice up even though the correct  
volume of refrigerant is present in the refrigerant circuit.  
A fault in the evaporator output temperature sender - G263-  
and / or a pressure/temperature sender could also cause the  
refrigerant circuit to ice up. With this complaint, therefore, also  
take note of the measured values of the various pressure/  
temperature senders in the refrigerant circuit ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating,  
air conditioning; Rep. gr. 00 ; Repair information; Checking  
cooling output (vehicle-specific workshop manual).  
Further notes regarding this ⇒ page 241 .  
250  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
Possible deviation from specification during pressure test  
High pressure normal  
Low pressure too low  
The requisite cooling output in the evaporator of the heating and air conditioning unit (and/or in the evap‐  
orator used to cool the high-voltage components) is not reached.  
Possible causes for deviation from specification and rectification  
♦ Too little refrigerant in circuit.  
♦ Actuation or function of the air conditioner compressor defective ⇒ Vehicle diagnostic tester in “Guided  
Fault Finding” mode.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning system, renew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system . If no fault can be found, extract the refrigerant.  
– Extract refrigerant from the refrigerant circuit ⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
– If the extracted refrigerant volume is considerably less than the specified fill volume (more than 100 g less)  
⇒ Heating, air conditioning; Rep. gr. 00 ; Technical data (vehicle-specific workshop manual), search for  
the leak and rectify the cause ⇒ “1.4 Investigating leaks”, page 68  
– The extracted refrigerant volume approximately equates to the prescribed fill volume, check actuation of  
the air conditioner compressor and the installed shut-off valves if no fault is found ⇒ Heating, air condi‐  
tioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual)  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves installed in the refrigerant circuit by means of the  
pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode  
and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– Depending on the result, repair the actuation or renew the defective component (air conditioner compres‐  
sor, shut-off valve, expansion valve, pressure/temperature sender) ⇒ Heating, air conditioning; Rep. gr.  
87 ; Refrigerant circuit (vehicle-specific workshop manual).  
– If no fault can be found, clean the refrigerant circuit (flush with R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
251  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
In the event of the following fault “High pressure normal, low  
pressure too low”, please note the following: With this fault,  
there is a chance that the evaporator in the heating and air  
conditioning unit could ice up even though the refrigerant vol‐  
ume in the circuit is OK.  
If the problem is with the air conditioner compressor (the air  
conditioner compressor is actuated at excessively high speed  
by the control unit for air conditioning compressor ), the refrig‐  
erant circuit does not have to be cleaned (by flushing with  
R1234yf refrigerant  
⇒ “1.6 Cleaning refrigerant circuit”, page 92 ). With this fault,  
it is sufficient to renew the air conditioner compressor (take  
note of refrigerant oil in air conditioner compressor and re‐  
plenish as necessary).  
If the expansion valve in front of the evaporator used to cool  
the high-voltage components is defective (or function and ac‐  
tuation are faulty), permanently closed or does not open far  
enough, the air conditioner compressor is likewise actuated  
with maximum output (the requisite temperatures in the heat  
exchanger are not reached). The pressure on the low pressure  
side then only drops to the specification or lower if, at the same  
time, no cooling output is required in the heating and air con‐  
ditioning unit. The air conditioner compressor extracts refrig‐  
erant on the low pressure from both evaporators. Since no  
refrigerant can flow through the expansion valve in the front  
heating and air conditioning unit, however, and the cooling  
output in the evaporator used to cool the high-voltage compo‐  
nents is not reached (there is a fault in the area of the evapo‐  
rator used to cool the high-voltage components), the electrical  
air conditioning compressor is actuated with a higher speed.  
However, no refrigerant can flow, which causes pressure on  
the low pressure side to drop below the specification. High  
pressure may not rise or only marginally as no energy ex‐  
change takes place. The same applies if a valve in the refrig‐  
erant circuit is not OK, if there is a fault with integration of the  
evaporator for cooling of the high-voltage components in the  
refrigerant circuit of the high-voltage system or a pump or  
valve installed there is not OK. Here, the heat exchanger for  
high-voltage battery does actually cool down but the cooled  
coolant does not reach the high-voltage components that need  
to be cooled down ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode and ⇒ Heating, air conditioning system; Rep.  
gr. 87 ; Coolant circuit (vehicle-specific workshop manual).  
lk  
A fault in the evaporator output temperature sender - G263-  
and / or a pressure/temperature sender could also cause this  
problem. Therefore, also take note of the measured values of  
the various pressure/temperature senders in the refrigerant  
circuit ⇒ Vehicle diagnostic tester in “Guided Fault Finding”  
mode and ⇒ Heating, air conditioning; Rep. gr. 00 ; Repair  
information; Checking cooling output (vehicle-specific work‐  
shop manual).  
Further notes regarding this ⇒ page 241 .  
252  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Possible deviation from specification during pressure test  
High pressure normal or too high  
Low pressure too high  
The air conditioner compressor is noisy (especially immediately after being switched on)  
The requisite cooling output in the evaporator of the front heating and air conditioning unit (and/or in the  
evaporator used to cool the high-voltage components) is not reached.  
Possible causes for deviation from specification and rectification  
♦ Actuation and function of air conditioner compressor faulty ⇒ Vehicle diagnostic tester in “Guided Fault  
Finding” mode.  
♦ One of the valves installed in the refrigerant circuit is defective or is not working properly ⇒ Heating, air  
conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-specific workshop manual).  
♦ One of the pressure/temperature senders or temperature sensors on or in the refrigerant circuit supplies  
incorrect values ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning;  
Rep. gr. 87 ; Overview of fitting locations - air conditioning system  
♦ Too much refrigerant in circuit.  
♦ Too much refrigerant oil in circuit.  
– Check the measured values of the various pressure/temperature senders and temperature sensors during  
operation of the air conditioning systeml,krenew components with false measured values ⇒ Vehicle diag‐  
nostic tester in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Overview of  
fitting locations - air conditioning system .  
– Check the actuation and function of the air conditioner compressor and repair ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode  
– Check the function and actuation of the various valves and pressure/temperature senders installed in the  
refrigerant circuit by means of the pressure distribution in the refrigerant circuit ⇒ Vehicle diagnostic tester  
in “Guided Fault Finding” mode and ⇒ Heating, air conditioning; Rep. gr. 87 ; Refrigerant circuit (vehicle-  
specific workshop manual).  
– If no fault can be found, extract the refrigerant from the refrigerant circuit.  
The quantity of refrigerant extracted is significantly greater than the prescribed charge quantity:  
– Recharge the refrigerant circuit and repeat the test.  
The quantity of refrigerant extracted is about equal to the prescribed charge quantity:  
– Check the actuation and function of the air conditioner compressor and the valves installed in the refrigerant  
circuit (shut-off valves and expansion valves) ⇒ Vehicle diagnostic tester in “Guided Fault Finding” mode.  
– Depending on the result, repair the actuation or renew the defective component (shut-off valve, expansion  
valve or air conditioner compressor as well as receiver/dryer) ⇒ Heating, air conditioning; Rep. gr. 87 ;  
Refrigerant circuit (vehicle-specific workshop manual).  
– If no fault can be found there may be too much refrigerant oil in the circuit. Clean the refrigerant circuit  
(flush with R1234yf refrigerant ⇒ “1.6 Cleaning refrigerant circuit”, page 92 ).  
Final measures  
– Recharge the refrigerant circuit ⇒ “2.6 Charging refrigerant circuit”, page 146  
– Repeat test  
⇒ “2.14.5 Checking pressures with air conditioning system switched on - vehicles with electrical air condi‐  
tioning compressor”, page 205  
2. Working with air conditioner service station  
GETth  
253  

Related Topics