Advertisement

Advertisement

Air conditioning system -> 2.4 Emptying refrigerant circuit for Your Volkswagen Touran 4 Door Second Generation (2015-2022)

Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
Note  
Connect the gas analysis device or air conditioner service station  
to the refrigerant circuit as instructed to do so, and bring it into  
operation ⇒ Operating instructions of gas analysis device ,  
⇒ page 131 and / or ⇒ Operating instructions air conditioner  
service station .  
lk  
If during the gas analysis it is found that the refrigerant in the cir‐  
cuit meets the specifications:  
– Turn the handwheel of the quick-release coupling adapter on  
the high pressure side no further than necessary to completely  
open the service connection (observe pressure gauge; do not  
over-tighten valve).  
– Perform the measures as required on the refrigerant circuit  
using the air conditioner service station .  
Note  
If, during the gas analysis, it is found that the R1234y refrig‐  
erant is contaminated, extract the refrigerant from the refrig‐  
erant circuit and send it back e.g. to your gas supplier for  
processing (or disposal)  
⇒ “2.13 Filling contaminated refrigerant in a recycling cylinder  
for analysis, processing or disposal”, page 161 ,  
⇒ “6.2.17 Returning contaminated R1234yf refrigerant for  
analysis, processing or disposal”, page 25 and  
⇒ “6.1 Basics of air conditioning technology”, page 16 .  
Should there be no means of doing this, extract the contami‐  
nated refrigerant immediately from the refrigerant circuit of the  
vehicle and collect in a recycling cylinder. Unscrew (close) the  
handwheel of the quick release coupling adapter on the low  
pressure side, switch off the air conditioner service station  
(and isolate from the power supply if necessary). Then sepa‐  
rate the quick release coupling adapter on the low pressure  
side from the vehicle. The quick release coupling adapter on  
the low pressure side must then be separated - e.g. with a  
suction hose from the workshop extraction unit - from the  
charge hose for the air conditioner service station and the  
contaminated refrigerant allowed to flow out of the charge  
hose into the extraction hose of the workshop extraction unit.  
To restore operational readiness of the air conditioner service  
station , reinstall the quick release coupling adapter on the low  
pressure side on the charge hose for the air conditioner serv‐  
ice station and evacuate using the air conditioner service  
station as instructed to do so in the relevant operating instruc‐  
tions ⇒ Operating instructions air conditioner service station .  
– Perform the measures as required using the air conditioner  
service station .  
⇒ “2.3 Performing gas analysis of refrigerant”, page 134  
⇒ “2.4 Emptying refrigerant circuit”, page 137 .  
⇒ “2.5 Evacuating refrigerant circuit”, page 140 .  
⇒ “2.6 Charging refrigerant circuit”, page 146 .  
⇒ “2.8 Switching off air conditioner service station and sepa‐  
rating from refrigerant circuit”, page 151  
⇒ “2.9 Charging refrigerant in reservoir”, page 153 .  
⇒ “2.10 Emptying air conditioner service station”, page 154 .  
2. Working with air conditioner service station  
GETth  
133  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
⇒ “2.14 Checking pressures”, page 170  
2.3  
Performing gas analysis of refrigerant  
Note  
For operation of the air conditioning system, it is important that  
the refrigerant used has a certain degree of purity.  
Contamination with other refrigerants or gases can cause  
damage and thereby failure of the air conditioning system.  
Contaminated refrigerant must be returned as gas of unknown  
composition e.g. to your gas supplier for processing (or dis‐  
posal) in accordance with legislative requirements ⇒ VW /  
Audi-ServiceNet .  
To prevent liquid components (e.g. droplets of refrigerant oil)  
in the extracted refrigerant gas from falsifying the result of the  
gas analysis, separators (filters) are installed in the gas anal‐  
ysis device that separate these droplets of liquid. Renew  
separators in accordance with specifications of gas analysis  
device or operating instructions of air conditioner service sta‐  
tion ⇒ Operating instructions of gas analysis device or ⇒  
Operating instructions of air conditioner service station .  
All vehicles  
– Connect the gas analysis device or air conditioner service sta‐  
tion to the refrigerant circuit as instructed to do so, and bring  
it into operation ⇒ Operating instructions of gas analysis de‐  
vice ,  
⇒ “2.2 Connecting air conditioner service station to refrigerant  
circuit”, page 131 and / or ⇒ Operating instructions air condi‐  
tioner service station .  
lk  
– Perform the gas analysis as per the operating instructions.  
Note  
A faulty gas analysis is possible from air in the refrigerant ho‐  
ses or non-observance of the procedure for gas analysis as  
detailed in the operating instructions.  
Carefully follow the operating instructions of the gas analysis  
device / air conditioner service station .  
Evacuate refrigerant hoses of the air conditioner service sta‐  
tion before connecting the service couplings to the refrigerant  
circuit / gas cylinder with R1234yf refrigerant hose (see oper‐  
ating instructions of gas analysis device / air conditioner serv‐  
ice station  
⇒ “2.3 Performing gas analysis of refrigerant”, page 134 .  
The gas analysis may provide the following results:  
♦ The R1234yf refrigerant complies with the specifications, the  
planned measures may be performed with the air conditioner  
service station .  
♦ A fault occurred during the gas analysis. The fault is to be in‐  
vestigated and rectified after which the gas analysis must be  
repeated.  
♦ The analysed R1234yf refrigerant does not comply with the  
specifications, the analysed refrigerant must be extracted as  
refrigerant of unknown composition and returned e.g. to your  
gas supplier for processing (or disposal)  
134  
Rep. gr.87 - Air conditioning system  
GETth  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
lk  
⇒ “6.2.17 Returning contaminated R1234yf refrigerant for  
analysis, processing or disposal”, page 25  
Note  
Should the analysis of the refrigerant - to be extracted e.g. from  
the refrigerant circuit of a vehicle - indicate that it is contami‐  
nated: you can also perform a gas analysis on the refrigerant  
e.g. of another cylinder from your gas supplier if you wish to  
verify the analysis result.  
Since R1234yf refrigerant is so pure, even small amounts of  
ambient air in the charge hoses of the air conditioner service  
station can falsify the results. For this reason, most air condi‐  
tioner service stations have a feature via which the gas anal‐  
ysis is repeated up to 2 times before a not OK result is  
displayed ⇒ Operating manual for air conditioner service sta‐  
tion .  
You can perform a simple function check on your gas analysis  
device e.g. using ambient air (unscrew the service coupling  
from the refrigerant hose with which the gas analysis is per‐  
formed and analyse the gas with the refrigerant hose open).  
The result of this test should then indicate that the analysed  
gas is not OK.  
The method of gas analysis employed here was developed for  
motor vehicle workshops. It provides no details about the pre‐  
cise composition of the refrigerant. This gas analysis can  
therefore only show how high the percentage of R1234yf re‐  
frigerant is in the refrigerant analysed. If the percentage of  
R1234yf is below 95%, the refrigerant does not comply with  
the specifications and can cause damage to the components  
of the refrigerant circuit. A gas analysis that also provides de‐  
tails about the precise composition of the analysed refrigerant  
is currently not available for workshops. Gas analyses with  
which the precise composition of gases can be investigated  
require complicated equipment and procedures and can usu‐  
ally only be performed with dedicated testing facilities.  
Should contaminated refrigerant be found during the gas analy‐  
sis, notify the customer before continuing work and bring the  
customer's attention to the following:  
There is contaminated refrigerant or refrigerant of unknown com‐  
position in the refrigerant circuit of his vehicle that does not  
comply with the vehicle manufacturer's specifications. This re‐  
frigerant:  
♦ must be returned e.g. to the gas supplier as refrigerant of un‐  
known composition for analysis, processing (or disposal)  
⇒ “6.2.17 Returning contaminated R1234yf refrigerant for  
analysis, processing or disposal”, page 25 .  
♦ can be the cause of a malfunction or may already have caused  
damage that makes the inevitability of malfunctions in the near  
future probable.  
♦ Depending on its composition, the use of contaminated refrig‐  
erant could lead to the operating permit of the vehicle being  
withdrawn.  
♦ If, as a result of contaminated refrigerant, internal damage to  
the refrigerant circuit has been caused (e.g. decomposition  
products of the contaminated refrigerant have affected the  
components of the refrigerant circuit  
⇒ “1.5 Renewing components”, page 79 ), the refrigerant cir‐  
cuit can only be restored to full functionality once all compo‐  
nents that came into contact with the contaminated refrigerant  
have been renewed. The internal condition of the refrigerant  
circuit can be appraised e.g. by visually inspecting certain  
2. Working with air conditioner service station  
GETth  
135  
Arteon 2018 ➤ , Atlas 2017 ➤ , CC 2012 ➤ , Caddy 2016 ➤ , Crafter 201 ...  
Air conditioning systems with refrigerant R1234yf - General information - Edition 07.2017  
components of the refrigerant circuit (e.g. the condition of the  
internal surfaces of removed refrigerant lines and refrigerant  
hoses, the internal surface of the refrigerant reservoir and the  
condition of the removed dryer cartridge).  
♦ If internal damage has been caused to the refrigerant circuit  
through contaminated refrigerant (e.g. failure of the air condi‐  
tioner compressor has ensued owing to damaged control  
elements or overheating, refrigerant oil has a stronger colour  
than usual but the parts containing refrigerant have not been  
affected ⇒ “1.5 Renewing components”, page 79 ), the refrig‐  
erant circuit can be charged again once it has been flushed  
(renew air conditioner compressor, dryer and expansion  
valve). However, since there is no way of anticipating the long-  
term effect of the contaminated refrigerant on the refrigerant  
oil and the components of the refrigerant circuit, no guarantee  
can be given in this case that the components of the refrigerant  
circuit will function correctly in future.  
♦ If the contaminated refrigerant has not caused internal dam‐  
age to the refrigerant circuit (e.g. the refrigerant oil does not  
have a stronger colour than usual, the components of the re‐  
frigerant circuit have not been affected), the refrigerant circuit  
can be charged again once the dryer has been renewed and  
the refrigerant circuit has been evacuated for an extended pe‐  
riod (at least 1 hour). However, since there is no way of  
lk  
anticipating the long-term effect of the contaminated refriger‐  
ant on the refrigerant oil and the components of the refrigerant  
circuit, no guarantee can be given in this case that the com‐  
ponents of the refrigerant circuit will function correctly in future  
⇒ “1.5 Renewing components”, page 79 .  
136  
Rep. gr.87 - Air conditioning system  
GETth  

Related Topics